ELECTRICAL
WIRING CONNECTIONS
A WARNING pjj^ hazard. Incorrect voltage can cause a fire or
seriously damage the motor and voids the warranty. The supply
voltage must be within ±10% of the motor nameplate voltage.
NOTICE: Dual-voltage motors are factorywired for 230 volts. If nec
essary, reconnect the motor for 115 volts, as shown. Do not alter
the wiring in single voltage motors.
Install, ground, wire, and maintain your pump in compliance with
the National Electrical Code (NEC) or the Canadian Electrical Code
CCEQ, as applicable, and with all local codes and ordinances that
apply. Consult your local building inspector for code information.
Motor wires
connect here.
-Power supply wires
connect here.
230 Volt:
Connect 2 hot wires (black and red)
here and cap the white (neutrai) wire. It does
not matter which wire goes to which screw.
115 Volt:
Connect one hot wire (black or red)
to one of these screws (it doesn't matter
which one). Conned the white (neutral) wire
to the other screw. Cap any remaining
L-■ black or red wires.
Clamp the power cable to prevent strain
on the terminal screws.
■ Connect the green (or bare copper) ground wire
to the green ground screw.
Connection Procedure:
1. Connect the ground wire first as shown in Figure 9. The ground
wire must be a solid copper wire at least as large as the power
supply wires.
2. There must be a solid metal connection between the pressure
switch and the motor for motor grounding protection. If the
pressure switch is not connected to the motor, connect the
green ground screw in the switch to the green ground screw
under the motor end cover. Use a solid copper wire at least as
lai^e as the power supply wires.
3. Connect the ground wire to a grounded lead in a service panel,
to a metal underground water pipe, to a metal well casing at
least ten feet (3M) long, or to a ground electrode provided by
the power company or the hydro authority.
4.
Connect the power supply wires to the pressure switch as
shown in Figure 6.
5. Reinstall the pressure switch cover.
FIGURE 6 - Pressure switch wiring
TABLE II - RECOMMENDED FUSING AND WIRING DATA
Pump Model
Motor
Horsepower
Volts
Max. Load
Amperes
Branch
Delayed Fuse
Rating Amps
Distance in Feet From Motor to Meter
Oto
50
51 to
100
101 to
200
201 to
300
Wire Size
390.2514
1/2
115/230
10.5/5.2
15/15
14/14
14/14
10/14
8/14
390.2518
3/4
115/230
12.4/6.2
20/15
12/14
12/14
10/14
8/14