User manual - optima ups 6k/ 10k (english) – XMART Optima 10K ISOTX User Manual
Page 27
USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)
______________________________________________________________________________________________________________________
20150105 Tower-Rack 6K-10K ISOTX
- 27
8.- OPERATION INTERFACE
UPS
FRONT
PANEL:
PUSH
BUTTON
RACK FRONT PANEL
TOWER FRONT PANEL
Both Rack and Tower type UPS offer same 4 function buttons as described below:
ON / ENTER
POWER ON : Keep selected during 1 second to power UPS ON.
ENTER : It Works as “ENTER” or confirmation function when LCD is in configuration menu mode.
OFF / ESCAPE
POWER OFF : Keep selected to turn UPS OFF.
ESCAPE : It Works as ESCAPE key when LCD is in configuration menu mode.
TEST / UP
BATTERY TEST : By selecting TEST key UPS enters into battery test mode during 10s.
UP : It Works as UP key when LCD is in configuration menu mode.
MUTE / DOWN
ALARM MUTE : It mutes alarm beep in progress.
DOWN : It Works as DOWN key when LCD is in configuration menu mode,
TEST / UP + MUTE / DOWN - Simultaneous Activation
CONFIGURATION MODE : When these 2 keys are activated at same time during 1s
UPS FRONT PANEL: LED INDICATOR LIGHTS
There are 4 LED indication lights in front panel, located below LCD. These 4 LEDs describe UPS condition as follow:
MODE
Bypass
Line
Battery Fault
UPS is in Auto-check mode during start-up.
●
●
●
●
BYPASS Mode
●
○
○
○
NORMAL Mode
○
●
○
○
BATTERY Mode
○
○
●
○
BATTERY TEST in progress
●
●
●
○
ECO Mode Activated
●
●
○
○
UPS in Failure
○
○
○
●
●
LED = ON /
○