GE Zenith Controls
7
■
■
ZTX-RM Operation and Maintenance Manual (62R-2000)
Automatic Transfer Generator
Testing (One Time Test)
Verify that the transfer switch
UTILITY
available and
position LEDs are illuminated.
Press and hold the
GENERATOR START
/
STOP
button
and the
TRANSFER
button for 5 seconds. This will
cause the generator to start. Once the generator has
started, the Generator LED will illuminate.
Once the
GENERATOR
power LED
has come on, the
transfer switch will now switch the load to the Generator.
The
GENERATOR
position LED will illuminate.
The transfer switch will be connected to the generator
for 5 minutes.
*
Then the switch will automatically return to
the utility and the
UTILITY
Position LED will illuminate.
The generator will cool down for 5 minutes (U Timer)
and then shut down. The
GENERATOR
LED
will go off.
This completes the automatic test.
Transfer Generator Testing
(Forcing Operation with Keypad)
Verify that the transfer switch
UTILITY
available and posi-
tion LEDs are illuminated.
Press and hold the
GENERATOR START
/
STOP
button for 5
seconds. This will start the generator.
Verify that the
GENERATOR
available LED
has illuminated.
Press the
TRANSFER
button. The switch will transfer
to the Generator source position. The
GENERATOR
position LED will now be illuminated.
Pressing the
TRANSFER
button again will cause the
unit to transfer to the utility power source. The
UTILITY
position LED will illuminate.
Pressing the
GENERATOR START
/
STOP
button will stop
the generator.
RM
4 Control Interface (
Optional
)
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, manual operation or removal of transfer switch or any of its components.
Connecting Engine Start may cause Generator to start. Before connecting, turn Generator OFF.
*
Pressing and releasing the generator Start/Stop button
will cancel current test.
C
C
D
B
F
A
B
F
C
D
B
F
+
A
B
+
LED
Diagnostic Flash Codes
Rapidly Flashing Generator
Availability
LED
n
Generator failed to start.
n
Generator starts but failed to reach proper
operating parameters.
n
Generator became over loaded for an extended
period of time.
n
Optional generator crank board (see generator
fault flash table on page 13)
Rapidly Flashing Generator
Position
LED
n
Switch did not transfer to Generator position.
Rapidly Flashing Utility
Position
LED
n
Switch did not transfer to Utility position.
C
D
B
I
C
I
I
NOTE:
All fault alarms can be cleared by
depressing the reset button.
NOTE:
Transfer will cause short interruption of power.