SPECIFICATIONS

GENERATOR SPECIFICATIONS

MDS45

KILOWATT

35 kW

KILOVOLT-AMPS (.8 PF)43.5 KVA
AMPERAGE

277/480 VOLT 3 PHASE 52 AMPS*
120/240 VOLT 3 PHASE 105 AMPS*
120/208 VOLT 3 PHASE 121 AMPS*
120/240 VOLT 1 PHASE 146 AMPS

*Based on .8 power factor at 130 degrees C.

Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).

GENERATOR RESISTANCE

MDS45

Main Stator

0.085 ohms

Main Rotor

3.2 ohms

Exciter Stator

0.35 ohms

Exciter Rotor

25 ohms

Exciter Voltage (F1-F2)

No Load

9.5 VDC

Full Load

36 VDC

Exciter Amperage (F1-F2)

No Load

0.4 Amps

Full Load

1.3 Amps

ENGINE SPECIFICATIONS

See Cummins Operation and Maintenance Manual for
complete engine specifications.

TRAILER/HOUSING

MDS45

Capacity

5000 lb.

Fuel Capacity

80 Gallons

Axles

Single

Hitch Height

Adjustable

Tires

P225/75R-15

Tire Pressure

35 psi

Sound Attenuated

ULTRA QUIET

Housing

Housing Standard

PREPARATION

NOTE: This booklet covers the entire unit, EXCEPT THE
ENGINE. See the engine manufacturer’s operator
manual for specific maintenance and care information
regarding the engine. Read ALL instructions in the
manuals provided before attempting to operate the
generator set.

UNPACKING

When receiving the unit, be sure to inspect it carefully for
freight loss or damage. Check the nameplate to be sure it
is what you ordered (proper kW, voltage, fuel, etc.). If
you have questions, contact your local authorized dealer.
If you see evidence of loss or damage at the time of
delivery, have the driver sign and describe the loss or
damage in the “memo of loss or damage” section on the
freight bill. Then contact the carrier to get instructions on
filing a claim.

When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is
referred to as “concealed damage.” Separate any dam-
aged material and contact the carrier for proper proce-
dures to file a “concealed damage” claim.

OIL REQUIREMENTS

This engine was filled at the factory. Before starting
check the oil level and ensure it is full. If not, fill to the
proper level with 15W-40 Cummins Premium Blue or
equivalent.

OIL QUANTITY

US Qt.

Liters

MDS45

8.0

7.5

FUEL REQUIREMENTS

See your engine operator's manual for complete type and
grade fuel information.

Filling the Fuel Tank

Standard Trailer - The standard trailer is equipped with a
single 80 gallon fuel tank. Use caution when filling the
tank not to overflow the tank into the trailer.

WARNING PERSONAL DANGER
Never refuel a running engine. Always stop the engine
and allow to cool before refueling.

Never allow the fuel tank to run completely empty, as air
may enter the fuel system making it necessary to bleed
the engine when restarting.