Winco RP25/B User Manual
Page 11

Page 9
2030-00
60706-226
VOLTAGE SELECTOR SWITCH
POSITION
TERMINALS MINIMUM
VOLTAGE
NORMAL
VOLTAGE
MAXIMUM
VOLTAGE
120/240 SINGLE PHASE
LINE TO LINE
L1 TO L3
220
240
260
120/240 VOLT RECEPTACLES
110/220
120/240
130/260
LINE TO NEUTRAL
L1 TO N
110
120
130
L2 TO N
-0-
-0-
-0-
L3 TO N
110
120
130
120 VOLT RECEPTACLES
110
120
130
120/208 THREE PHASE
LINE TO LINE
ALL
200
208
220
120/240 VOLT RECEPTACLES
110/200
120/208
127/220
LINE TO NEUTRAL
ALL
115
120
127
120 VOLT RECEPTACLES
ALL
115
120
127
G3 TO N
115
120
127
120/240 THREE PHASE
LINE TO LINE
ALL
220
240
260
120/240 VOLT RECEPTACLES
110/220
120/240
130/260
LINE TO NEUTRAL
USE CAUTION THIS CONFIGU-
RATION HAS A HIGH VOLTAGE
LEG
G1 TO N
110
120
130
HIGH VOLTAGE LEG
G2 TO N
191
208
225
G3 TO N
110
120
130
120 VOLT RECETPACLES
110
120
130
277/480 THREE PHASE
LINE TO LINE
ALL
416
460
480
120/240 VOLT RECEPTACLE
NONE
NONE
NONE
LINE TO NEUTRAL
ALL
240
265
277
120 VOLT RECETPACLE
NONE
NONE
NONE
The table below show the voltages at the terminal lug as well as the receptacles
for all four voltage patterns available through the selector switch.
WARNING - POTENTIAL EQUIPMENT DAMAGE
THE 120/240 VOLT THREE PHASE POSITION HAS A WILD LEG THAT PRODUCES 208 VOLTS LINE TO
NEUTRAL ON G2. BE SURE WHEN CONNECTING TO YOUR PANEL OR LOAD THAT YOU MATCH THE
WILD PHASE ON THE GENERATOR TO THE WILD PHASE IN YOUR PANEL OR LOAD. FAILURE TO DO
SO WILL RESULT IN 12O VOLT DEVICES RECEIVING 208 VOLTS. YOU MUST ALSO MATCH YOUR
ROTATION.