D.c. electrical connections, Control panel layout – Winco ULPSS90/A WITH BASLER DGC-2020 ENGINE CONTROL User Manual
Page 11
60706-194
Page 9
0210-10
B - Generator Circuit Breaker, This circuit breaker provides
overload protection for the generator. Your power feeds from the
transfer switch will connect to the bottom lugs on the circuit
breaker. The generator power feeds have already been wired
into the upper lugs.
The table below gives you the circuit breaker size, lug wire sizes
and torque specification. (see the actual breaker for additional
information and restrictions)
kW
Voltage PH
Amp
Wire Capability
Lug Torque
90
120/240
1
350
#1 AWG - 600 MCM 375 in lbs
90
120/208
3
300
#1 AWG - 600 MCM 375 in lbs
90
120/240
3
250
#1 AWG - 600 MCM 375 in lbs
90
277/480
3
125
#14 - #3/0 AWG
120 in lbs
60
120/240
1
250
#1 AWG - 600 MCM 375 in lbs
60
120/208
3
200
#4 AWG - 300 MCM 250 in lbs
60
120/240
3
175
#4 AWG - 300 MCM 250 in lbs
60
277/480
3
90
#14 - #3/0 AWG
120 in lbs
Minimum Conductor Sizes between the Generator and the ATS.
Based on wire type and temperature rating. Wire has been
derated for 40
o
C ambient temperatures.
Cu Conductor
Al Conductor
C/B
Wire Temperature Rating
kW Voltage PH Amp 75
0
C
90
0
C
75
0
C
90
0
C
90 120/240 1
350
600 MCM 500 MCM (NOTE 1) 600 MCM
90 120/208 3
300
500 MCM 350 MCM 600 MCM 500 MCM
90 120/240 3
250
300 MCM 250 MCM 500 MCM 350 MCM
90 277/480 3
125
1/0 AWG #1 AWG
3/0 AWG 2/0 AWG
60 120/240 1
250
300 MCM 250 MCM 500 MCM 350 MCM
60 120/208 3
200
4/0 AWG 3/0 AWG 300 MCM 250 MCM
60 120/240 3
175
3/0 AWG 2/0 AWG 250 MCM 4/0 AWG
60 277/480 3
90
#2 AWG #3 AWG
1/0 AWG #2 AWG
NOTE 1 TWO 250 MCM MAY BE USED.
For additional information on wire sizing refer to table 310-16 of
the National Electrical Code ANSI/NFPA 70.
C - Ground Lug, These ground lugs are bonded to ground and
are provided for you to connect your ground wire from the transfer
switch to. The lugs on the 80 kW will handle wire sizes #1 AWG
to 300 MCM and should be torqued to 250 in. lbs. The lugs on
the 60 kW will accommodate #1 AWG to 250 MCM and should
be torqued to 250 in. lbs.
D. 120 Volt Terminal Block, This terminal block is provide for the
120 volt/ 15 amp feed from customers distrubution panel for the
block heater and the trickle charger.
**************
***** WARNING *****
**************
A main line circuit breaker has been provided inside the genera-
tor housing. During all wiring installations make sure the breaker
is in the off position and the generator operation switch is in the
off position.
**************
***** WARNING *****
**************
EQUIPMENT DAMAGE - When installing a Three Phase 240 volt
system be sure you know which lead is the high voltage "wild" leg
(208 Volt line to neutral). The generator normally carries the high
voltage on the G2 lead.
The load current carrying wires (L) and (T) must be sized to
handle the maximum load current without excessive voltage drop.
By code, the wire must be heavy enough to handle the full current
rating of the main line circuit-breaker (or fuse) in the entrance (or
sub-panel) protecting the contactor switch.
All wires should be installed in rigid or flexible conduit. (Knock-
outs are provided in the connection box).
See the manual shipped with the Automatic Transfer Switch for
connection locations in the switch. Connections in each switch
will vary depending on the type of switch and the manufacturer.
GROUNDING
A grounding lug has been provided on the engine generator set
to grounded to earth ground if required. Check with your local
codes. Generally a 6 foot copper rod driven into the earth will
provide a proper earth ground.
D.C. ELECTRICAL
CONNECTIONS
NOTE:
There are varies DC connectors on the engine that have
nothing connected to them. This was done intentional, these
connectors are for END OF LINE TESTING and other various
diagnostic tests. There are not used during normal opera-
tions and can just be ignored.
All DC connections are completed in the small box just below the
engine control cabinet. In addition there are two small fuses
mounted on the bottom of the engine control cabinet that protect
both the engine control and all the other DC connections.
CONTROL PANEL LAYOUT
A - DGC-2020 Digital Gen-Set Control. See Explanation on
page 3.