Unpacking instructions, Specifications – Winco ULPSS40/F WITH DSE 7110 CONTROL (2011) User Manual
Page 5
60706-212
Page 3
1270-10 REV B
ENGINE SPECIFICATIONS:
Refer to engine operating and maintenance instructions
** NOTICE **
Regarding Engines - This manual covers the generator portion of
these units. See the separate engine instruction manual for
engine-related problems, detailed engine information and engine
warranty.
** CAUTION **
EQUIPMENT DAMAGE - Be sure to check the engine oil level
frequently as specified in the engine manual.
The engine manufacturer has established an excellent worldwide
engine service organization; engine service is available from a
nearby authorized dealer or distributor; check the Yellow Pages
of the telephone directory under “engines,” or ask the dealer from
whom you purchased the power plant.
The rated power of each engine-generator is limited by the
temperature, altitude and all other ambient conditions specified
by the engine manufacturer. Engine power will decrease 3-1/2%
for each 1000 ft. above sea level, and will decrease an additional
1% for each 10
o
Fahrenheit above 60
o
Fahrenheit. Units should
not be operated in ambient temperature greater than 40
o
C.
UNPACKING INSTRUCTIONS
** NOTICE **
When unpacking the generator set, be sure to inspect it carefully
for freight loss or damage. If loss or damage is noted at the time
of delivery, require that the person making the delivery make note
of the loss or damage on the freight bill, or affix his signature
under the consignees’s memo of the loss or damage. Contact
the carrier for claim procedures.
When loss or damage is noted after delivery, segregate the
damaged material, and contact the carrier for claim procedures.
“Concealed Damage” is understood to mean damage to the
contents of a package which is not in evidence at the time of
delivery by the carrier, but which is discovered later. The carrier
or carriers are responsible for merchandise lost or damaged in
transit. The title to goods rests with the consignee when genera-
tors are shipped FOB factory, and only the consignee can legally
file a claim.
**** CAUTION ****
EQUIPMENT DAMAGE - These units are shipped with oil, and a
50/50 mix of coolant. Be sure to check all fluid levels before
operating. See engine manufacturer’s instruction manual for
recommended oil requirements before initial starting.
FUNCTIONS
DSE 7110 Series Control Modules perform the following protec-
tion and metering functions:
Generator Protection and Metering
Generator protection includes over voltage, under voltage, under
frequency, over frequency and overload protection. Each genera-
tor protection function has an adjustable pickup and time delay
setting. Metered generator parameters include voltage, current,
real power (watts), power factor (PF)
Engine Protection and Metering
Engine protection features include oil pressure and coolant
temperature monitoring, over crank protection, ECU specific
protection elements, and diagnostic reporting.
Metered engine parameters include, oil pressure, coolant
temperature, battery voltage, speed, engine load, coolant level
(from ECU), ECU specific parameters, and run-time statistics.
** NOTICE **
These units will automatically transfer if a power outage occurs
while running in an exercise mode.
SPECIFICATIONS
GENERATOR
MODEL
WATTS
VOLTS
AMP
HZ
PH
RPM
PSS30-3
30,000
120/240
125.0*
60
1
1800
PSS30-4
30,000
120/208
104.2**
60
3
1800
PSS30-17
30,000
120/240
90.3**
60
3
1800
PSS30-18
30,000
277/480
45.1**
60
3
1800
PSS40-3
40,000
120/240
166.7*
60
1
1800
PSS40-4
40,000
120/208
138.9**
60
3
1800
PSS40-17
40,000
120/240
120.4**
60
3
1800
PSS40-18
40,000
277/480
60.2**
60
3
1800
*Unity Power Factor - Derate 3.5% per 1000 feet elevation above
sea level.
**Power Factor .8 - Derate 3.5% per 1000 feet elevation above
sea level.
FUEL CONSUMPTION
NG (1,000 BTU/CU FT) L.P. VAPOR (2,520 BTU/CU FT)
MODEL
CF/HR
BTU/HR
#/HR GAL/HR CF/HR
BTU/HR
PSS30
432
432,000
20.4
4.9
172
442.049
PSS40
499
498,907
25.0
5.9
210
541.012
L.P. TANK SIZING
Minimum required L.P. Tank size for L.P. Vapor withdrawal
operating at various outside temperatures given in degrees
Fahrenheit (Celsius)
TANK TEMPERATURE
MODEL
60 F(16 C)
30 F(0 C) 0 F(-18 C)
-20 F(-29 C)
PSS30
160 Gal
300 Gal
1000 Gal*
2000 Gal*
PSS40
250 Gal.
500 Gal.
1000 Gal.*
2000 Gal.*
*Recommend liquid withdrawal at these temperatures.