Winco ULPSS21/A WITH DSE 7310 ENGINE CONTROL User Manual
Page 7

60706-227
Page 5
2090-00
LP LIQUID WITHDRAWAL SYSTEMS
When installing a unit equipped the LP liquid withdrawal a
primary regulator is not required on the supply tank. The supply
line is connected to a liquid withdrawal valve on the supply tank
and runs directly to the fuellock strainer mounted on the engine
generator set. Normally a 3/8 to 1/2 inch copper line is accept-
able for this type of fuel installation. You must be sure that the
valve you have connected to on the supply tank is in fact a liquid
supply valve and has a drop tube inside the tank that is pulling
fuel from the bottom of the supply tank. Before starting the unit
you must confirm that you have a good liquid supply at the unit.
Engine generator sets equipped for liquid withdrawal will not
run properly when supplied with high pressure vapor fuel.
LUBRICATION
Before starting the engine, check the oil level in the crankcase. If
it is low, refill to the full mark with the proper weight/grade of oil as
recommended by the engine manufacturer’s maintenance
instructions. The necessity of using the correct oil, and keeping
the crankcase full cannot be over emphasized. Failure to use the
proper oil and keep the crankcase properly filled will cause
excessive engine wear and shorten its useful life.
COOLANT
Before starting the engine, check the coolant level in radiator. If it
is low, refill as specified in the engine manufacturer’s mainte-
nance instructions. The radiator should be filled to about 1 inch
below the filler neck. For additional information on engine coolant
requirements see engine manufacturer’s maintenance instruc-
tions.
INSTALLING THE BATTERY
**** CAUTION ****
In the following battery installation procedure, check to be sure
the selector switch remains in the “stop” position. This should be
your last step before initial start-up.
A customer supplied twelve-volt battery is required to complete
the installation. Installation of the highest CCA rated battery,
within the correct BCI group, will increase cold weather starting
performance. Gel batteries should not be used with the battery
tender installed in the generator enclosure.
MINIMUM
Model
Voltage
BCI Group CCA Rating
PSS21
12
24
650
Installation and servicing of batteries must be performed or
supervised only by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away from
batteries.
When installing or replacing batteries, use the proper group/size
starting battery. The battery should be a Maintenance Free lead
acid design. Deep cycle batteries will not work for this applica-
tion.
Supply
Primary
Secondary
Generator
Tank
Regulator
Regulator
Set
1 2
3
4
TWO (2) REGULATOR FUEL SYSTEM
Supply
Primary
Generator
Tank
Regulator
Set
1
2
4
SINGLE REGULATOR FUEL SYSTEM
Reference numbers 1 through 3 in the block diagrams above are
fuel lines supplied by customer.
Reference number 4 is the engine generator set.
Below is a table of the fuel pressure readings at each reference in
the system.
Fuel Pressure Table
Single Regulator (L.P. Vapor only)
1
2
3
UNIT OFF
TANK PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
STARTING
TANK PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
NO LOAD
TANK PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
FULL LOAD
TANK PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
Two (2) Regulator System (L.P. Vapor only)
1
2
3
4
UNIT OFF
TANK PSI
10-15 lbs
7-11 in
7-11 in
4-6 oz.
4-6 oz.
STARTING
TANK PSI
10-15 lbs
7-11 in
7-11 in
4-6 oz.
4-6 oz.
NO LOAD
TANK PSI
10-15 lbs
7-11 in
7-11 in
4-6 oz.
4-6 oz.
FULL LOAD TANK PSI
10-15 lbs
7-11 in
7-11 in
4-6 oz.
4-6 oz.
Natural Gas
1
2
4
UNIT OFF
LINE PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
STARTING
LINE PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
NO LOAD
LINE PSI
7-11 in
7-11 in
4-6 oz.
4-6 oz.
FULL LOAD
LINE PSI
7-11 in.
7-11 in
4-6 oz.
4-6 oz.
Notice the preceding tables give two (2) different units of measur-
ing fuel pressure. The first is with a pressure gauge calibrated in
ounces per square inch. The second and most accurate is the
use of a simple water manometer. A manometer is calibrated in
inches of water column.