TESTING POLICY:
Before any generator is shipped from the factory, it is
fully checked for performance. The generator is loaded
to its full capacity, and the voltage, current, and frequency
are carefully checked.
Rated output of generators is based on engineering
tests of typical units, and is subject to, and limited by, the
temperature, altitude, fuel, and other conditions specified
by the manufacturer of the applicable engines.
INTRODUCTION AND DESCRIPTION
The package standby system includes all items
necessary for a completely automatic standby power
system as standard equipment.
DESCRIPTION
This packaged standby system is designed to auto-
matically provide standby power to unattended loads
during electrical outages. Upon an interruption of normal
electrical service the packaged standby system electrical
control circuits will automatically start the engine. The
generator will produce electrical power and the Automatic
Transfer Switch (A.T.S.) will automatically transfer the
electrical loads to the engine-generator set. Upon
restoration of normal electrical service the emergency
transfer switch will sense return of the normal commer-
cial power. The Automatic Transfer Switch will retransfer
the load back to the normal commercial power source.
The engine control circuits will begin a cool-down cycle,
after which the fuel supply will be shut off and the engine
ignition system disabled.
These packaged standby systems consist of two
major components:
1) AUTOMATIC TRANSFER SWITCH
A wall mounted Automatic Transfer Switch (A.T.S.)
designed for inside installation. The A.T.S. consists of a
line side contactor and a generator side contactor. The
contactors are both electrically and mechanically
interlocked. A seven day electronic exerciser clock is
installed in the A.T.S. as standard equipment. The A.T.S.
also contains the power failure sensing circuitry neces-
sary to send a start/stop signal to the engine generator
set.
Automatic Transfer Switch Sizes
(NON-UL)
UNIT
LINE SIDE
GENERATOR
CONTACTOR
SIDE CONTACTOR
PSS10H
110 AMPS
60 AMPS
PSS12H
110 AMPS
60 AMPS
UL Automatic Transfer Switch Sizes
UNIT
LINE SIDE
GENERATOR
CONTACTOR
SIDE CONTACTOR
PSS10H &
100 AMPS
100 AMPS
PSS12H
200 AMPS
200 AMPS
Both the 100 amps and the 200 amps UL Switches are
available in single and three phase.
Additional optional A.T.S. sizes are available to meet
specific needs. Contact your local WINCO dealer, or the
WINCO Sales Department for a quote.
2) ENGINE/GENERATOR
The engine generator set consists of a Honda, twin
cylinder, four cycle air cooled engine. The engine is
factory equipped to run on L.P. or N.G. fuel. The engine
operates at 3600 rpm and frequency regulation is
maintained by the engine governor within 4 cycles
variation (62.5 Hz - 58.5 Hz) from no load to rated load.
The generator is a brushless, single bearing, direct drive,
rotating field design. The generator is connected to the
engine’s tapered (quill) crankshaft extension. The
engine generator is mounted in a NEMA 3R enclosure for
outside installation. Connection boxes are provided for
all customer connections (both AC output and DC
control). A customer supplied 235 CCA (BCI group U1)
battery is required to complete the installation. Engine
operation is controlled by an Electronic Engine Control
Module (E.C.M.) mounted in the engine generator
enclosure. The E.C.M. is equipped standard with a 10
second start delay, 90 second cool down delay and cycle
cranking.
** NOTICE **
This unit will automatically transfer if a power outage
occurs while running in an exercise mode.
SPECIFICATIONS
GENERATOR
MODEL
WATTS* VOLTS
AMPS*
HZ
PH
RPM
PSS10H
9,600
120/240
40.0
60
1
3600
PSS12H
12,000
120/240
50.0
60
1
3600
*Derate 16% for Natural Gas operation. Derate 3.5%
per 1000 feet elevation above sea level.
FUEL CONSUMPTION
NG
L.P. VAPOR
1000 BTU/CU FT
2520 BTU/CUFT
MODEL CF/HR
BTU/HR
#/HR* GAL/HR
CF/HR BTU/HR*
PSS10H
160
160,000
7.7
1.80
70.2
180,000
PSS12H
190
190,000
9.0
2.10
76.6
194,000
*Based on full load operation