beautypg.com

Winco PSS8B2W/C User Manual

Page 13

background image

PAGE 11

8008-30

60706-182

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to
automatically exercise the generator for 20 minutes once
every fourteen days .

In order to set and test the exercise circuit the right
hand toggle switch on the generator control panel
must be in the normal position.

SETTING THE EXERCISER CIRCUIT

Press and release the Automatic Generator Exerciser
button. After about 8 seconds the exerciser light flashes
14 times to indicate that the exerciser circuit has been
set. The number of flashes indicates the number of days
until the next exercise period. This 20 minute period will
occur at approximately the same time of the day the
button was pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the Automatic Generator Exerciser
button until the light above the button goes off, the light
flashes and then goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the Automatic Generator Exerciser
button until the light goes off, the light flashes then goes
off. After about 8 seconds the exerciser light flashes
fourteen times to indicate that the exerciser circuit has
been re-enabled.

*************
***** WARNING *****
*************
WITH A TOTAL POWER FAILURE (UTILITY POWER
FAILS AND THE GENERATOR FAILS TO START AND
RUN) THE EXERCISER MUST BE RESET AFTER THE
POWER IS RESTORED.

Once you are finished testing the transfer switch, this
completes your installation and unit testing. ALWAYS
leave the system in automatic mode unless servicing the
unit. For automatic operation, keep both the generator set
and transfer selector switches in the “AUTOMATIC”
position.