PAGE 5

regulator in the fuel line will interfere with each other.
When this two (2) stage regulator system is used, a
fuel line size of 1/2 to 5/8 inch is generally adequate
for distances up to 300 feet from the primary to the
secondary regulator. (Consult your local fuel supplier
for your exact requirements.) The appropriate line size
from the table below is then installed from the second
regulator to the generator set.

*************
***** WARNING ****
*************
PERSONAL DANGER - Do not use galvanized pipe in

fuel line runs. The galvanized coating can become
eroded and flake off, causing possible obstructions in
the regulator or fuel valve. The results could range
from inoperative engine start to hazardous fuel leaks.

Size of pipe normally required for generators operating on

NATURAL GAS or LP vapor

up to 25 feet*

25 - 100 feet*

over 100 feet*

PSS8000

3/4" pipe

1" pipe

not recommended

PSS12000

3/4” pipe

1” pipe

use a two

PSS20000

1" pipe

1.25" pipe

regulator system

*Allow an additional 3 feet for each standard elbow. Do not use
‘street ells’ (restrictive)*

Size of pipe normally required for generators operating on

LP liquid withdrawal

PSS20000 - 3/8” line for all distances.

**** CAUTION ****

Be careful when sealing gas joints. Excessive sealing

compound can be drawn into the solenoid, regulator or
carburetor causing an engine malfunction.

FUEL PRESSURE

L.P. & N.G. VAPOR FUEL

Correct fuel pressure cannot be stressed enough. The

most common cause for inoperative systems is an
inadequate or incorrect fuel pressure. Performance of
the engine is in direct relation to the correctness of the
fuel system. Shown below is a block diagram of a
typical L.P. or N.G. vapor fuel installation.

Notice the following tables give two (2) different units of

measuring fuel pressure. The first and most accurate
is the use of a simple water manometer. A manometer
is calibrated in inches of water column. The second is
with a pressure gauge calibrated in ounces per square
inch.

TWO (2) REGULATOR FUEL SYSTEM

Supply

Primary

Secondary

Generator

Tank

Regulator

Regulator

Set

1

2

3

4

SINGLE REGULATOR FUEL SYSTEM

Supply

Primary

Generator

Tank

Regulator

Set

1

3

4

Reference numbers 1 through 3 in the block diagrams

above are system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each

reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only)

1

3 4

UNIT OFF

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only)

1

2

3

4

UNIT OFF

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

Natural Gas

1

3

4

UNIT OFF

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz