Cleaning, Troubleshooting, Generator specifications – Winco WL12000HE/K User Manual
Page 13: Engine specifications

13
2015-00
60706-233
2.
Generator Maintenance - Any major generator
service, including the installation or replacement
of parts, should be performed only by a qualified
electrical service technician.
USE ONLY FACTORY
APPROVED REPAIR PARTS.
a. Bearing - The bearing used in these generators
is a heavy duty double sealed ball bearing.
They require no maintenance or lubrication.
b. Receptacles - Quality receptacles have been
utilized. If a receptacle should become cracked
or otherwise damaged, replace it. Using dam-
aged or cracked receptacles can be both dan-
gerous to the operator and destructive to the
equipment.
CLEANING
Remove dirt and debris with a cloth or brush. DO
NOT use high pressure spray to clean either the
engine or the generator. This high pressure spray
could contaminate the fuel system and the genera-
tor components.
1. Keep the air inlet screen on both the engine and
generator free of any dirt or debris to insure proper
cooling. At least yearly, remove the blower housing
on the engine and clean the chaff and dirt out of the
engine cooling fins and flywheel. Clean more often
if necessary. Failure to keep these areas clean may
cause overheating and permanent damage to the
unit.
2. Periodically clean muffler area to remove all
grass, dirt and combustible debris to prevent a fire.
3. On engine mufflers equipped with spark arrest-
ers, the spark arrester must be removed every 50
hours for cleaning and inspection. Replace if dam-
aged
TROUBLESHOOTING
PROBLEM (SYMPTOMS) POSSIBLE
CAUSES
———————————————————————
Won’t Start
*Low Oil Level.
*Fouled spark plug.
*Out of fuel.
*Start switch in Off position.
*Fuel valve turn off.
*Plugged fuel filter.
*Blown fuse in key switch
———————————————————————
Voltage too low
*Engine speed is too low.
*Generator overloaded.
*Defective stator.
*Defective rotor (field).
*Defective Capacitor.
———————————————————————
Circuit Breaker
*Defective load.
Trips
*Defective receptacle.
*Excessive Load.
———————————————————————
Voltage too high
*Engine speed is too high.
———————————————————————
Generator
*Overloaded.
overheating
*Insufficient ventilation.
———————————————————————
No output voltage
*Short in load (disconnect).
*Tripped or defective circuit
breaker.
*Broken or loose wire.
*Defective receptacle.
*No residual magnetism
(in generator).
*Defective stator.
*Defective rotor (field).
*Shorted capacitor.
*Shorted diodes on rotor.
*GFCI Receptacle tripped.
———————————————————————
GENERATOR SPECIFICATIONS
Generator manufacturer
MECC Alte Spa
Generator model number
S20FS-160A
Part number
351836-1
Rotor resistance
6.57 Ohms
Stator resistance
0.124 Ohms
Cap winding resistance
0.60 Ohms
Capacitors
31.5 mF
Capacitor part number
300323-112
ENGINE SPECIFICATIONS
Engine manufacturer
HONDA
Engine model number
GX630R
Type
VXE1 NH1
Code
653951
Spark plugs
ZFR5F (NGK)
Air filter
17210-Z6L-000
Air filter pre-cleaner
17218-Z6L-000
Oil filter
15400-RTA-004
Air Filter
16910-Z6L-003
Spark plug gap
0.030 in
Intake valve clearance
0.006 - 0.010 in
Exhaust valve clearance
0.010 - 0.012 in
Oil capacity
57 - 58 oz.