Refrigeration – Shellab SRI20-2 User Manual
Page 11

11
Unit will not heat up at all
1/ verify that controller is asking for heat by looking for controller light
– if
pilot light is not on continuously, there is a problem with the controller. 
2/ check amperage 
– amperage should be virtually at maximum rated
(data plate) amperage. 
3/ do all controller functions work? 
4/ is the Thermostat set high enough? 
– for diagnostics, should be fully
clockwise with the pilot light never on. 
5/ has the fuse/circuit breaker blown? 
Indicated chamber temperature unstable
1/ ±0.1 may be normal 
2/ is fan working? 
– remove top panel and verify movement of cooling fan
in center of shadow box 
3/ is ambient room temperature radically changing 
– either door opening
or room airflow from heaters or air conditioning ?
– stabilize ambient
conditions. 
4/ sensor miss-located, damaged or wires may be damaged - check 
mounts for control and Thermostat sensors, then trace wires or tubing 
between sensors and controls. 
5/ calibration sensitivity 
– call Customer Service
6/ Overtemperature set too low
– be sure that the thermostat is more
than 5 degrees over desired set point; check if OVERTEMP pilot is on 
continuously; turn controller knob completely clockwise to see if problem 
solved then follow instructions in owner’s manual for correct setting – see 
section 5.7 
7/ electrical noise 
– remove nearby sources of RFI including motors,
arcing relays or radio transmitters. 
8/ bad connection on temperature sensor or faulty sensor 
– check
connectors for continuity and mechanical soundness while watching 
display for erratic behavior; check sensor and wiring for mechanical 
damage. 
9/ bad connections or faulty relay 
– check connectors for mechanical
soundness and look for corrosion around terminals or signs of arcing or 
other visible deterioration. 
Will not maintain set point
1/ assure that set point is at least 5 degrees over ambient - 
2/
SEE IF AMBIENT IS FLUCTUATING
Display and reference thermometer don’t 
match 
1/ calibration error
– see section 5.6
2/ temperature sensor failure
– evaluate if pilot light is operating
correctly. 
3/ controller failure 
– evaluate if pilot light is operating correctly
4/ allow at least two hours to stabilize. 
5/ see if reference thermometer is certified. 
Can't adjust set points or calibration
1/ turn entire unit off and on to reset. 
2/ if repeatedly happens, call Customer Service 
Calibrated at one temperature, but not at 
another 
This can be a normal condition when operating temperature varies widely. 
For maximum accuracy, calibration should be done as close to the set 
point temperature. 
REFRIGERATION
Temperature can't get up to set point
1/ assure that power is going to heating coils. 
2/ if the displacement is erratic, see if air is being circulated. 
3/ confirm that controller is calling for heat (check front panel light). 
4/ if light not coming on, check control set point and Overtemperature set 
point . 
5/ confirm that fan is operating and airflow is not blocked. 
6/ reset by turning unit off and on. 
