Rogue Engineering ROGUE TERRAIN User Manual
Page 4

4
ROGUE TERRAIN OFF GRID POWER SUPPLY ENCLOSURE
INSTALLATION
The Rogue Terrain enclosure may be wall mounted or pole mounted .
If wall mounted the device shall be secured to the wall utilizing appropriate
customer-provided mounting apparatus .
If pole mounted, the slots in the flanges at the top and bottom of the enclosure
will accommodate a variety of sizes of U-bolts that may be used with a round
pole .
EXTERNAL POWER WIRING
Ensure that the Battery, Solar and Load fuses are removed from the
corresponding three black DIN mounted fuseholders .
External battery, solar and load wiring should use, at minimum, AWG 14
stranded copper wire and industry convention would dictate that all external
positive wiring should be red and negative (ground) wiring should be black .
Extend red and black wires from solar panel(s) into the rear cable grip at the
bottom of the enclosure and terminate on the designated Solar (+) and Solar
(-) terminals as identified on the wiring diagram on the inside cover of the
enclosure . Wire ends should be stripped at 3/8 inch . Terminal screws should
be tightened securely using the screwdriver provided on the inside cover of
the enclosure .
Extend red and black wires from the load into the front cable grip at the
bottom of the enclosure and terminate on the designated Load (+) and Load
(-) terminals as identified on the wiring diagram on the inside cover of the
enclosure . Wire ends should be stripped at 3/8 inch . Terminal screws should
be tightened securely using the screwdriver provided on the inside cover of
the enclosure .
If an internal battery is to be utilized, open the buckle on the web retaining
strap and set the battery at the bottom of the enclosure with the terminals
nearest the right end of the battery . Secure the battery with the web strap
and buckle, adjusting the buckle to hold the battery tightly in place . Connect
the red and black connectorized battery leads to the spade connectors on the
battery .
If an external battery is to be used, extend red and black wires from the battery
into the center cable grip at the bottom of the enclosure . Disconnect the
existing short connectorized red and black battery leads from the Battery
(+) and Battery (-) terminals as identified on the wiring diagram on the
inside cover of the enclosure and connect the external battery wiring to the
corresponding terminals . Wire ends should be stripped at 3/8 inch . Terminal
screws should be tightened securely using the screwdriver provided on the
inside cover of the enclosure .