Physical description, Setup, Important notes – Crestron electronic GLA-PWS50 User Manual
Page 4: Supplied hardware

50 Watt Cresnet Power Supply
Crestron GLA-PWS50
Physical Description
This section provides information on the connections,
controls and indicators available on the GLA-PWS50.
GLA-PWS50 Overall Dimensions
5.55 in
(14.09 cm)
4.00 in
(10.16 cm)
5.03 in
(12.77 cm)
2.15 in
(5.45 cm)
0.12 in
(0.31 cm)
GLA-PWS50
Connectors, Controls & Indicators
# CONNECTORS,
CONTROLS &
INDICATORS
DESCRIPTION
1
LINE POWER
(3) 6” flying leads, 18 AWG, line
power input
Hot (black), neutral (white), and
ground (green/yellow)
connections
2
OUTPUT
(2) 6” flying leads, 18 AWG,
Cresnet power output
+24 VDC (red), G (black/white)
connections
Connects to “24” and “G”
connections of the Cresnet
control network, or directly to a
24 Volt DC powered Crestron
device
3
FUSE
DC output fuse, T3.15AH
(5x20mm, 250V, 3.15A, time-
lag, ceramic cartridge).
4
24VDC LED
(1) green LED, indicates 24
Volts DC output, extinguishes
when fuse is blown
Setup
Important Notes
Read before installation.
• Permits: An electrical permit shall be obtained
prior to each installation.
• Codes: Install in accordance with all local and
national electrical codes.
• Wiring: Use 75°C copper wire only.
• Disconnect device: An appropriate and readily
accessible disconnect device shall be provided as
part of the building installation wiring.
• To ensure adequate branch circuit protection, use
an overcurrent protective device rated 15 or 20
amps.
• Not suitable for Hazardous/Classified areas.
Supplied Hardware
The hardware supplied with the GLA-PWS50 is listed in
the following table.
Supplied Hardware for the GLA-PWS50
DESCRIPTION PART
NUMBER
QUANTITY
Partition 2022663
1
Plastic Rivet
2005423
3
Twist-On Wire Connector
2005432
5
4
• Wall Mount 50 Watt Cresnet Power Supply: GLA-PWS50
Installation Guide – DOC. 6734B