beautypg.com

Physical description, Setup, Important notes – Crestron electronic GLA-PWS50 User Manual

Page 4: Supplied hardware

background image

50 Watt Cresnet Power Supply

Crestron GLA-PWS50

Physical Description

This section provides information on the connections,
controls and indicators available on the GLA-PWS50.

GLA-PWS50 Overall Dimensions

5.55 in

(14.09 cm)

4.00 in

(10.16 cm)

5.03 in

(12.77 cm)

2.15 in

(5.45 cm)

0.12 in

(0.31 cm)

GLA-PWS50

Connectors, Controls & Indicators

# CONNECTORS,

CONTROLS &

INDICATORS

DESCRIPTION

1

LINE POWER

(3) 6” flying leads, 18 AWG, line
power input

Hot (black), neutral (white), and
ground (green/yellow)
connections

2

OUTPUT

(2) 6” flying leads, 18 AWG,
Cresnet power output

+24 VDC (red), G (black/white)
connections

Connects to “24” and “G”
connections of the Cresnet
control network, or directly to a
24 Volt DC powered Crestron
device

3

FUSE

DC output fuse, T3.15AH

(5x20mm, 250V, 3.15A, time-
lag, ceramic cartridge).

4

24VDC LED

(1) green LED, indicates 24
Volts DC output, extinguishes
when fuse is blown

Setup

Important Notes

Read before installation.

• Permits: An electrical permit shall be obtained

prior to each installation.

• Codes: Install in accordance with all local and

national electrical codes.

• Wiring: Use 75°C copper wire only.

• Disconnect device: An appropriate and readily

accessible disconnect device shall be provided as
part of the building installation wiring.

• To ensure adequate branch circuit protection, use

an overcurrent protective device rated 15 or 20
amps.

• Not suitable for Hazardous/Classified areas.

Supplied Hardware

The hardware supplied with the GLA-PWS50 is listed in
the following table.

Supplied Hardware for the GLA-PWS50

DESCRIPTION PART

NUMBER

QUANTITY

Partition 2022663

1

Plastic Rivet

2005423

3

Twist-On Wire Connector

2005432

5

4

Wall Mount 50 Watt Cresnet Power Supply: GLA-PWS50

Installation Guide – DOC. 6734B