4-10 Compaq 3000 Series UPS Operation and Reference Guide
Table 4-2
Operating Ranges (VAC) – North America and Japanese Models
Nominal Level
Normal Range
Extended Range
100
80 to 120
Not applicable for R3000j
110
88 to 132
72 to 132
120
96 to 144
78 to 144
127
102 to 152
83 to 155
Table 4-3
Operating Ranges (VAC) – All High Voltage Models
Nominal Level
Normal Range
Extended Range
208
166 to 250
Not applicable for
R3000h-NA
220
176 to 264
143 to 264
230
184 to 276
150 to 276
240
192 to 288
156 to 288
3.
For nominal voltage level setting, select configuration parameters
1, 2, 3, or 10 (see Table 4-1).
4.
Access parameter 4 to switch from normal to extended range (see
Table 4-1).