Eclipse Combustion 6500 User Manual
Page 42
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
42
Table 10.2
Remote Display Diagnostic Messages (continued)
MESSAGE
TYPE
EXPLANATION
Hold
Flame signal—actual, induced, or faulty scanner—is detected be-
fore start-up or after shutdown. The fan is energized. If the cause
is corrected within 30 seconds, as in afterburn, the control will
turn off the fan and continue the sequence.
Lockout
Same conditions as above, except the cause has not been corrected
within 30 seconds, resulting in a lockout and alarm.
Hold
Flame signal—actual, induced, or faulty scanner—is detected dur-
ing the selected purge time period. The fan is energized. If the
cause is corrected within 30 seconds, as in afterburn, the control
will turn off the fan and continue the sequence.
Lockout
Same conditions as above, except the cause has not been corrected
within 30 seconds, resulting in a lockout and alarm.
Status
Indicates that the optional valve leak sensing device has been acti-
vated and the test period “XX” has begun.
Lockout
The test period for valve leak sensing has exceeded XX seconds
and failed; check the gas shut-off valves.
Lockout
Internal control failure; replace controller.
Status
In combination with other messages, shows the control is in the
minimum pilot test mode.
UNSAFE FLAME ON
UNSAFE FLAME ON
LKOUT XXXX:XX:XX
UNSAFE–FLM–PURGE
UNSAFE–FLM–PURGE
LKOUT XXXX:XX:XX
VALVE LEAKAGE
UNDER TEST XX
VALVE LEAK FAIL
LKOUT XXXX:XX:XX
WATCHDOG FAIL
LKOUT XXXX:XX:XX
XXXXXXX
XXXXXTESTXX