Calibrating the Slant Valve

The roll (slant) valve can only be calibrated manually as described below. When calibrating the
roll valve you must first calibrate the deadzone clockwise and counter clockwise settings and
then the gain clockwise and counter clockwise settings.

Navigating to the Slant Valve Settings:

1. Ensure the UC4+ control panel is in manual mode, at the run screen.

2. Toggle "SETUP" until the display shows "More?". Toggle "AUTO (YES)" to confirm.

3. Toggle "SETUP" until the display shows "Roll?". Toggle the "AUTO (YES)" switch to

confirm.

4. Toggle the "SETUP" switch to access the next menu prompt or toggle "SENSOR DISPLAY"

to access the previous menu. Choose the dead zone up/down or gain up/down setting
(Figure 3).



Roll Channel On

Roll Channel Dead Zone Clockwise (cw)

Roll Channel Gain Clockwise (cw)

Roll Channel Dead Zone Counter Clockwise (ccw)

Roll Channel Gain Counter Clockwise (ccw)

Figure 3: Slant Valve Settings


KP

5

KP

5

Roll OnU

DZ 20

DZ 20

Sensor

Display

Setup