Example- Command:

**430

Response:

Channel four normal state is closed

NOTE:

If C=5, the Power Fault channel, the response is:

Example Command:

**531

Response:

Power fault channel is ENABLED

Command: **530

Response:

Power fault channel is DISABLED


NOTE:

When channel 5 is configured OFF it will not call out when a power
failure occurs.


NOTE:

If C=6 or C=7, the Temperature Fault channel, the response is:

Example Command:

**630

Response:

Low Temperature fault Channel is DISABLED

Command: **631

Response:

Low Temperature fault Channel is LOCAL

Command: **632

Response:

Low Temperature fault Channel is INPUT

I/O Return-To-Normal Status Selection of channel c return to normal status

notification. When enabled, the input channel’s return to a normal state after an
alarm will cause a notification callout, using the same list of telephone numbers to
call as an alarm event.


NOTE: Unlike Alarm events, once acknowledged there is NO snooze operation.


*c4

Review I/O channel c return-to-normal configuration

**c41/0

Program I/O channel c return-to-normal configuration

Example- Command:

**141

Response:

Channel one alarm clear status is enabled.

Example- Command:

**440

Response:

Channel four alarm clear status is disabled.


I/O Alarm Setpoint Selection of Low or High Temperature Alarm Setpoints.

Channel 6 is the Low Temperature channel, and Channel 7 is the High Temperature
channel. The following command allows the Low or High temperature alarm
Setpoint to be configured or queried.


NOTE: This command is only valid for c = 6 (Low Temperature) or c = 7 (High

Temperature).