beautypg.com

Bsi series - bermuda, Technical specifications – Crown Boiler BSI069 User Manual

Page 2

background image

www.crownboiler.com | Philadelphia PA

BSI SERIES - BERMUDA

TECHNICAL SPECIFICATIONS

MODEL

NO. OF

SECS

NATURAL OR LP GAS

AFUE %

APPROX.

SHIPPING

WEIGHT

(PKG)

DIMENSIONS

(INCHES)

INPUT
(MBH)

HEATING

CAPACITY

(MBH)

AHRI NET RATING

(STEAM)

A

B

C

FLUE

COLAR

DIAMETER

SQ. FT.

MBH

BSI069

3

69

56

179

49

81.9

354

12-3/4

28

40-7/16

4

BSI103

4

103

84

267

73

82.0

432

16

28

40-7/16

5

BSI138

5

138

113

354

98

82.1

504

19-1/4

28

40-7/16

6

BSI172

6

172

142

446

123

82.2

589

22-1/2

28

40-7/16

6

BSI207

7

207

171

533

149

82.3

669

25-3/4

30

40-7/16

7

BSI241

8

241

200

621

174

82.4

745

29

30

40-7/16

7

BSI276

9

276

229

708

199

82.5

826

32-1/4

30

40-7/16

8

BSI311

*

10

310

253

790

190

77.5**

957

35-1/2

30

45-7/16

8

BSI346

*

11

345

281

879

211

77.5**

1044

38-3/4

30

45-7/16

9

BSI380

*

12

379

309

966

232

77.5**

1125

42

30

45-7/16

9

1. USA - For altitudes above 2,000 ft. ratings should be reduced at the rate of 4% for each 1,000 ft above sea level.

Available as semi-packaged boiler

*Not available for elevations above 2,000 ft. or for use with LP gas

**Thermal efficiency

Specifications are subject to change without notice.

All residential cast iron steam boilers include a full one-year
warranty. A 12-year limited warranty is provided for the heat
exchanger. A 5-year and a 10-year extended warranty covering
parts and labor are also available. Visit CrownBoiler.com or see
your warranty for complete details.

The Mega-Stor

®

indirect water heater utilizes the

energy created by your boiler to produce abundant
hot water for your home. Mega-Stor water heaters
come in a variety of sizes from 26 to 119 gallons to
meet a multitude of residential and commercial
needs.

ADDITIONAL FEATURES/BENEFITS
• Available with natural or LP gas
• Probe low water cut-off standard; option of float low water

cut-off or low water cut-off/feeder combo

• Isolation relay simplifies thermostat wiring
• Redundant gas valve
• Roll-out switch; blocked vent switch
• Glass gauge set

12

-YEA

R LIMITE

D

WARRANTY

BSI - 08/12

PN 980531 - R4