Heater table (allen-bradley), With general electric switches, Heater table (general electric) – Cooper Bussmann EDSC2199 User Manual
Page 2

463
www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright
©
2010 Cooper Crouse-Hinds
2C
2C
EDS Series Factory Sealed
Manual Motor Starting Switches
and Enclosures
Ordering Information
With Allen-Bradley Bulletin 600 Switches
Maximum HP Ratings
Poles
115–230
Volts AC
115–230
Votts DC
Cat. #
1
1 hp
A B BUL 600 TOX4
2
1 hp
3
/
4
hp
A B BUL 600 TOX5
Poles
Hub
Size in.
Dead end Cat. #
Through feed Cat. #
Single Gang
1
3
/
4
EDS2199
➀
EDSC2199
➀
1
EDS3199
➀
EDSC3199
➀
2
3
/
4
EDS21100
➀
EDSC21100
➀
1
EDS31100
➀
EDSC31100
➀
Two Gang
1
3
/
4
EDS2299
➀
EDSC2299
➀
1
EDS3299
➀
EDSC3299
➀
2
3
/
4
EDS22100
➀
EDSC22100
➀
1
EDS32100
➀
EDSC32100
➀
Heater Table (Allen-Bradley)
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
0.17
P1
2.92
P22
0.21
P2
3.09
P23
0.25
P3
3.32
P24
0.32
P4
3.77
P25
0.39
P5
4.16
P26
0.46
P6
4.51
P27
0.57
P7
4.93
P28
0.71
P8
5.43
P29
0.79
P9
6.03
P30
0.87
P10
6.83
P31
0.98
P11
7.72
P32
1.08
P12
8.24
P33
1.19
P13
8.9
P34
1.30
P14
9.6
P35
1.43
P15
10.8
P36
1.58
P16
12.0
P37
1.75
P17
13.5
P38
1.88
P18
15.2
P39
2.13
P19
2.40
P20
2.58
P21
With General Electric Switches
Maximum HP Ratings
Poles
115–230
Volts AC
115
Votts DC
230
Votts DC
Cat. #
1
1 hp
1 hp
1
/
4
hp
GE CR101 Y
2
1 hp
1 hp
1 hp
GE CR101 H
Poles
Hub Size
in.
Dead end Cat. #
Through feed Cat. #
Single Gang
1
3
/
4
EDS21093
➀
EDSC21093
➀
1
EDS31093
➀
EDSC31093
➀
2
3
/
4
EDS21094
➀
EDSC21094
➀
1
EDS31094
➀
EDSC31094
➀
Two Gang
1
3
/
4
EDS22093
➀
EDSC22093
➀
1
EDS32093
➀
EDSC32093
➀
2
3
/
4
EDS22094
➀
EDSC22094
➀
1
EDS32094
➀
EDSC32094
➀
Heater Table (General Electric)
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
.48
G2
3.01
G22
.53
G3
3.27
G23
.58
G4
3.56
G24
.65
G5
3.88
G25
.71
G6
4.22
G26
.78
G7
4.60
G27
.86
G8
5.00
G28
.95
G9
5.43
G29
1.04
G10
5.90
G30
1.14
G11
6.41
G31
1.25
G12
6.98
G32
1.37
G13
7.60
G33
1.49
G14
8.25
G34
1.63
G15
8.95
G35
1.78
G16
9.75
G36
1.95
G17
10.6
G37
2.13
G18
11.4
G38
2.32
G19
12.5
G39
2.53
G20
13.6
G40
2.76
G21
14.8
G41
16.0
G42
Cl. I, Div. 1 & 2, Groups B*, C, D
Cl. II, Div. 1, Groups E, F, G
Cl. II, Div. 2, Groups F, G
Cl. III
NEMA 3, 7B*CD, 9EFG
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
*Add GB suffix. Seals must be installed within 1
1
/
2
" of each conduit opening for Group B usage.
➀ Includes one interchangeable heater. Select heater from the table
below individual listings and use symbol number as second section
of the Cat. No. Example: EDS2199-P5. Insert symbol 0 (zero) to omit
heater.
These heaters are for motors rated 40°C continuously. For motors
rated 50°C or 55°C, multiply full load motor current by 0.9 and use
this value to select heaters. Symbol 0 (zero) must be used to indicate
heater omitted.