Specifications and ordering information – Cooper Bussmann POWERPATH PS-6 User Manual
Page 3
POWERPATH™ Operating Modes (refer to Installation Manual):
Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening
on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated.
Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification
appliances. Audibles can also be silenced in this mode while the strobes continue to flash.
In>Out Sync Mode: Accepts a synchronization signal on the input to provide a coded output or synchronized output. This signal
may come from a FACP, another POWERPATH or a Wheelock DSM synchronization module. Caution: Do not use strobes on coded
output circuits.
True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the
input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes
on coded output circuits.
Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns,
bells or chimes. Caution: Do not use strobes on coded output circuits.
Specifications and Ordering Information
Model Number
Order
Code
Input Voltage/Current
Approvals
UL
CSFM FM
PS-6
105530
6 amp, red enclosure
X
X
X
PS-6B
100257
6 amp, black enclosure
X
X
X
PS-8
105531
8 amp, red enclosure
X
X
X
PS-8B
105830
8 amp, black enclosure
X
X
X
PS-6EXP
105083
6 amp power supply with preinstalled expansion module
X
X
X
PS-8EXP
105084
8 amp power supply with preinstalled expansion module
X
X
X
PS-EXP
105534
4 class B or 2 class A expansion module
X
X
X
PS-EXP-RETRO
105527
Field upgrade kit for models prior to January 2010
#
X
X
X
Input Circuit
Input Voltage and Current
Input voltage Range
8 to 33 VDC
Input Current @ 12 VDC
0.005 amps
Input Current @ 24 VDC
0.005 amps
Output Circuit
Output Voltage and Current
Four (4) Class B or
24 VDC @ up to 3 amps per curcuit
Two (2) Class A or
One (1) Class A and Two (2) Class “B” or
8 Class B or 4 Class A
(optional PS-EXP module necessary)
Continuous duty up to 3 Amps per circuit, up to 4 Amps maximum per panel
Standby Current
0.129 Amps
Alarm Current
0.129 Amps
Primary PS-6 (120 VAC models)
105 to 130 VAC, 50/60 Hz @ 4.25 Amps
Primary PS-8 (120VAC models)
105 to 130 VAC 50/60 Hz @ 5.32 Amps
Primary PS-6E (240 VAC models)
210 to 260 VAC, 50/60 Hz @ 2.42 Amps
Primary PS-8E (240 VAC models)
210 to 260 VAC 50/60 Hz @ 3.22 Amps
Secondary Power Charging Capacity
32 Amp hours @ 0.750 Amps per hour
Enclosure can house up to two 12 AH batteries
Aux Output
CP Mode
PS-6 up to 75 mA
PS-8 up to 250 mA
MP Mode
2.5A during non alarm
Model
Dimensions
Weight
Comments
PS-6/PS-6B
17”H x 13”W x 3.5”D
11.5lbs. (Ship) 9.4lbs (Unit)
Small profile
PS-8/PS-8B
17”H x 15”W x 5.5”D
17.7lbs (Ship) 15.6lbs (Unit)
Additional room for modules
PS-EXP
4.3”H x 3.7”W x 1”D
1lb. (Ship & Unit)
Plugs into main pcb on all
models
X= Approved
*= Pending
#=Contact Technical
Support for additional
inforamation on upgrade
options