beautypg.com

Specifications and ordering information – Cooper Bussmann POWERPATH PS-6 User Manual

Page 3

background image

POWERPATH™ Operating Modes (refer to Installation Manual):
Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening

on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated.
Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification

appliances. Audibles can also be silenced in this mode while the strobes continue to flash.
In>Out Sync Mode: Accepts a synchronization signal on the input to provide a coded output or synchronized output. This signal

may come from a FACP, another POWERPATH or a Wheelock DSM synchronization module. Caution: Do not use strobes on coded

output circuits.
True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the

input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes

on coded output circuits.
Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns,

bells or chimes. Caution: Do not use strobes on coded output circuits.

Specifications and Ordering Information

Model Number

Order

Code

Input Voltage/Current

Approvals

UL

CSFM FM

PS-6

105530

6 amp, red enclosure

X

X

X

PS-6B

100257

6 amp, black enclosure

X

X

X

PS-8

105531

8 amp, red enclosure

X

X

X

PS-8B

105830

8 amp, black enclosure

X

X

X

PS-6EXP

105083

6 amp power supply with preinstalled expansion module

X

X

X

PS-8EXP

105084

8 amp power supply with preinstalled expansion module

X

X

X

PS-EXP

105534

4 class B or 2 class A expansion module

X

X

X

PS-EXP-RETRO

105527

Field upgrade kit for models prior to January 2010

#

X

X

X

Input Circuit

Input Voltage and Current

Input voltage Range

8 to 33 VDC

Input Current @ 12 VDC

0.005 amps

Input Current @ 24 VDC

0.005 amps

Output Circuit

Output Voltage and Current

Four (4) Class B or

24 VDC @ up to 3 amps per curcuit

Two (2) Class A or
One (1) Class A and Two (2) Class “B” or
8 Class B or 4 Class A

(optional PS-EXP module necessary)
Continuous duty up to 3 Amps per circuit, up to 4 Amps maximum per panel

Standby Current

0.129 Amps

Alarm Current

0.129 Amps

Primary PS-6 (120 VAC models)

105 to 130 VAC, 50/60 Hz @ 4.25 Amps

Primary PS-8 (120VAC models)

105 to 130 VAC 50/60 Hz @ 5.32 Amps

Primary PS-6E (240 VAC models)

210 to 260 VAC, 50/60 Hz @ 2.42 Amps

Primary PS-8E (240 VAC models)

210 to 260 VAC 50/60 Hz @ 3.22 Amps

Secondary Power Charging Capacity

32 Amp hours @ 0.750 Amps per hour

Enclosure can house up to two 12 AH batteries

Aux Output
CP Mode

PS-6 up to 75 mA

PS-8 up to 250 mA

MP Mode

2.5A during non alarm

Model

Dimensions

Weight

Comments

PS-6/PS-6B

17”H x 13”W x 3.5”D

11.5lbs. (Ship) 9.4lbs (Unit)

Small profile

PS-8/PS-8B

17”H x 15”W x 5.5”D

17.7lbs (Ship) 15.6lbs (Unit)

Additional room for modules

PS-EXP

4.3”H x 3.7”W x 1”D

1lb. (Ship & Unit)

Plugs into main pcb on all

models

X= Approved

*= Pending

#=Contact Technical

Support for additional

inforamation on upgrade

options

This manual is related to the following products: