Eclipse AH-MA Air Heat Burner v2, Design Guide 160, 8/1/05
24
Figure 3.10 Staged Burner Valve Layout
Note:
A single pilot fuel feed can be used when the staged burners are
piloted by the adjacent burners.
Consult Eclipse
Eclipse can help you design and obtain a main gas shut-off valve train that
complies with the current safety standards.
The shut-off valve train must comply with local safety standards set by
authorities that have jurisdiction.
For details, please contact your local Eclipse representative or Eclipse
Combustion.
Note:
Eclipse supports NFPA regulations (two shut-off valves) as a
minimum standard for main gas safety shut-off valves.