Troubleshooting honeywell vs8421 – Vermont Casting NV360 User Manual
Page 15
15
Vermont Castings Majestic Products NV360/580 Series
20003565
Remove glass door before service work
START
CHECK
Gas Supply On
▼
▼
▼
▼
▼
Pilot Lights With Piezo
Ignitor
•
Lockout Has Engaged. Wait 60
Seconds And Try Again.
•
For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.
•
All Wiring Connections
•
Replace Piezo Ignitor
•
Supply Line Hooked Up
•
Shut off Valve Open
Pilot Stays Lit
•
For Air In The Lines
•
Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
•
All Wiring Connections
•
Replace Thermopile
•
Thermocouple Needs A Min. Of
14mv
•
Defective Valve. Turn To Pilot,
Meter Should Read Greater
Than 100mv. If Not, Replace.
Pilot Lights Main Burner
•
Valve Is Turned On
•
Wall Switch Is Not Turned On.
Watch For Grounded Wires!
•
Thermopile Needs A Min. 325mv.
•
Plugged Burner Orifice
System Ok
▼
YES
NO
NO
▼
NO
▼
NO
YES
YES
YES
Troubleshooting
Honeywell VS8421
- RHE32 (38 pages)
- R24CFL (14 pages)
- 3399 (38 pages)
- DVRT41 (48 pages)
- Montpelier Wood Insert MEAD3CB (12 pages)
- Insert Studio LHER30 (8 pages)
- SR18SHK (16 pages)
- PerfectView 33LDV (4 pages)
- SC42 (24 pages)
- 3030 (26 pages)
- EF22 (16 pages)
- DV360 (56 pages)
- DV580 (60 pages)
- SA24SKHRN (20 pages)
- SHR42A (24 pages)
- VL21 (20 pages)
- DEF (11 pages)
- 7TDVP8 (3 pages)
- DVRT39 (50 pages)
- HiStyle DVBR42RN (2 pages)
- ICVCTK01 (12 pages)
- RFSDV24 (36 pages)
- HEF22 (12 pages)
- NVBC42 (24 pages)
- VCEF33 (12 pages)
- Romanesque HG004 (4 pages)
- Designer Select Series (4 pages)
- OD24SHKN (12 pages)
- BR36 (24 pages)
- CVR36 (28 pages)
- H33BDVRRNP (32 pages)
- 2080 (24 pages)
- DEF33 (16 pages)
- Allura-Fire Electric Fireplaces EF26 (1 page)
- EF26 (2 pages)
- DBR33 (32 pages)
- DEF33CE (12 pages)
- HEF33 (14 pages)
- D232 (28 pages)
- RHEDV25 (38 pages)
- Allura-Fire Markham Combo MKWWH33 (2 pages)
- BREF42R (24 pages)
- DBT39 (34 pages)
- CR36R (24 pages)