beautypg.com

Operating instructions – ebm-papst W6E710-GR03-01 User Manual

Page 5

background image

Operating instructions

W6E710-GR03-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M6E110-IA

Phase

3~

Nominal voltage / VAC

230

Frequency / Hz

50

Type of data definition

ml

Valid for approval /
standard

CE

Speed / min

-1

900

Power input / W

630

Current draw / A

2.79

Motor capacitor / µF

14

Capacitor voltage / VDB

450

Max. back pressure / Pa

105

Min. ambient temperature
/ °C

-40

Max. ambient
temperature
/ °C

65

Starting current / A

6.9

Maximum safe operating
speed / min

-1

1140
@ 70 °C

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

33.4

28.3

32.3

Efficiency grade N

41.1

36

40

Power input P

e

/ kW

0.61

Air flow q

v

/ m³/h

7510

Pressure increase total p

sf

/ Pa

99

Speed n / min

-1

900

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

27.3 kg

Size

710 mm

Surface of rotor

Cast in aluminium

Material of terminal box

PP plastic

Material of blades

Aluminium sheet insert, sprayed with PP
plastic

Material of wall ring

Sheet steel, galvanised and coated in
black plastic (RAL 9005)

Material of guard grille

Steel, coated in black plastic (RAL9005)

Number of blades

5

Blade angle

-10°

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F3-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box, integrated capacitor
connected via terminal box

Motor protection

Thermal overload protector (TOP)
brought out

Cable exit

Axial

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC; VDE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 10159-5-9970 · Revision 82513 · Release 2014-07-16 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com