beautypg.com

Operating instructions – ebm-papst W3G500-GM56-21 User Manual

Page 9

background image

Operating instructions

W3G500-GM56-21

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Colour

Function / assignment

1

1,2

PE

green/
yellow

Protective earth

1

3

N

blue

Supply voltage, neutral conductor, 50/60 Hz

1

4

L

black

Supply voltage, phase, 50/60 Hz

1

5

COM

white 1

Floating status message contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)

1

6

NC

white 2

Floating status message contact, break for failure

2

8

0-10 V

yellow

Control input, set value 0-10 VDC, impedance 100 kΩ, SELV

2

11

10 VDC

red

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for external devices (e.g.
potentiometer), SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no. 50427-5-9970 · Revision 83181 · Release 2014-06-04 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com