beautypg.com

Operating instructions – ebm-papst W1G172-EC91-01 User Manual

Page 5

background image

Operating instructions

W1G172-EC91-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M1G055-BD

Phase

1~

Nominal voltage / VAC

230

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

2500

Power input / W

22

Current draw / A

0.18

Max. back pressure / Pa

60

Min. ambient temperature
/ °C

-30

Max. ambient
temperature
/ °C

50

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Technical features

Mass

0.848 kg

Size

172 mm

Material of impeller

PA plastic 6, fibreglass-reinforced

Material of wall ring

Plastic, PPTD 20

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"B"

Humidity class

F3-1

Mounting position

Any

Condensate discharge
holes

None

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Over-temperature protected motor
- Soft start
- Speed selection max/min

Speed steps

2

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Lateral

Protection class

II

Product conforming
to standard

CE

Approval

CSA C22.2 Nr.77; EAC; UL 2111; VDE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.5 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.6 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2

EMC harmonics

Acc. to EN 61000-3-2/3

EMC interference
emission

Acc. to EN 61000-6-3

Item no. 50079-5-9970 · Revision 82579 · Release 2014-05-08 · Page 5 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com