Operating instructions – ebm-papst S4E560-AQ01-01 User Manual
Page 5
Operating instructions
S4E560-AQ01-01
Translation of the original operating instructions
3.2 Nominal data
Motor
M4E110-IA
Phase
1~
Nominal voltage / VAC
230
Frequency / Hz
50
Type of data definition
ml
Valid for approval /
standard
CE
Speed / min
-1
1275
Power input / W
1090
Current draw / A
4.76
Motor capacitor / µF
20
Capacitor voltage / VDB
450
Max. back pressure / Pa
160
Min. ambient temperature
/ °C
-40
Max. ambient
temperature
/ °C
55
Maximum safe operating
speed / min
-1
1650
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category
A
Efficiency category
Static
Variable speed drive
No
Specific ratio
*
1.00
*
Specific ratio = 1 + p
fs
/ 100 000 Pa
Actual
Request
2013
Request
2015
Overall efficiency η
es
/ %
29.9
29.9
33.9
Efficiency grade N
36
36
40
Power input P
e
/ kW
1.09
Air flow q
v
/ m³/h
6485
Pressure increase total p
sf
/ Pa
174
Speed n / min
-1
1270
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass
20 kg
Size
560 mm
Surface of rotor
Cast in aluminium
Material of terminal box
ABS plastic, black
Material of blades
Aluminium sheet insert, sprayed with PP
plastic
Material of guard grille
Steel, phosphated and coated in black
plastic
Number of blades
5
Blade angle
-5°
Direction of air flow
"V"
Direction of rotation
Counter-clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"F"
Humidity class
F3-1
Mounting position
Shaft horizontal or rotor on bottom; rotor
on top on request
Condensate discharge
holes
Rotor-side
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Electrical leads
Via terminal box, integrated capacitor
connected via terminal box
Motor protection
Thermal overload protector (TOP)
brought out
Cable exit
Axial
Protection class
I (if protective earth is connected by
customer)
Product conforming
to standard
EN 61800-5-1; CE
Approval
EAC; VDE
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+ 80 °C
Min. permissible
ambient motor temp.
(transp./storage)
- 40 °C
Item no. 10855-5-9970 · Revision 82543 · Release 2014-05-08 · Page 5 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com