3.2 Nominal data

Motor

M4D110-IA

Phase

3~

3~

Nominal voltage / VAC

400

400

Connection

Δ

Y

Frequency / Hz

50

50

Type of data definition

ml

ml

Valid for approval /
standard

CE

CE

Speed / min

-1

1330

1070

Power input / W

1250

840

Current draw / A

2.48

1.42

Max. back pressure / Pa

150

100

Min. ambient temperature
/ °C

-40

-40

Max. ambient
temperature
/ °C

55

55

Starting current / A

10

Maximum safe operating
speed / min

-1

1540
@ 70 °C

1540
@ 70 °C

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

37.9

30.5

34.5

Efficiency grade N

43.4

36

40

Power input P

e

/ kW

1.35

Air flow q

v

/ m³/h

8830

Pressure increase total p

sf

/ Pa

210

Speed n / min

-1

1310

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

16.2 kg

Size

630 mm

Surface of rotor

Cast in aluminium

Material of terminal box

PP plastic

Material of blades

Aluminium sheet insert, sprayed with PP
plastic

Material of guard grille

Steel, coated in black plastic (RAL9005)

Number of blades

5

Blade angle

-10°

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F3-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP)
brought out

Cable exit

Axial

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC; VDE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 10103-5-9970 · Revision 82542 · Release 2014-05-08 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com