beautypg.com

Operating instructions – ebm-papst A3G630-AC52-51 User Manual

Page 8

background image

Operating instructions

A3G630-AC52-51

Translation of the original operating instructions

4.4 Connection screen

No.

Conn.

Designation

Colour

Function / assignment

1

1,2

PE

green/
yellow

Protective earth

1

3

N

blue

Supply voltage, neutral conductor, 50/60 Hz

1

4

L

black

Supply voltage, phase, 50/60 Hz

1

5

COM

white 1

Floating status message contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)

1

6

NC

white 2

Floating status message contact, break for failure

2

8

0 - 10 V

yellow

Control input, set value 0 - 10 VDC, impedance 100 kOhm, SELV

2

11

10 VDC

red

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices (e.g. potentiometer),
SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no. 50179-5-9970 · Revision 82624 · Release 2014-05-08 · Page 8 / 11