beautypg.com

Operating instructions – ebm-papst R3G710-AP02-01 User Manual

Page 8

background image

Operating instructions

R3G710-AP02-01

Translation of the original operating instructions

4.3.2 Connecting cables with terminals

WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

; Remove the cap from the screwed cable gland.
Remove the cap only in those places where cables are inserted.
; Mount the screwed cable glands with the seal inserts provided in the

terminal box.

; Insert the line(s) (not included in the standard scope of delivery) into

the terminal box.

; First connect the "PE" (protective earth) connection.
; Connect the lines to the corresponding terminals.
Use a screwdriver to do so.
During the connection work, ensure that no cables splice off.

Fig. 2: Connecting the wires to terminals
; Seal the terminal box.

4.3.3 Cable routing

No water may penetrate along the cable in the direction of the cable gland.
When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 3: Cable routing for fans installed upright.

4.4 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Control mode
parameter set 1

PWM controlling

Control mode
parameter set 2

PWM controlling

Fan / device adress

1

Max. PWM / %

100

Min. PWM / %

5,1

Save set value to
EEPROM

Yes

Set value control

Analogue (linear)

Control function
parameter set 1

Positive (heating)

Control function
parameter set 2

Positive (heating)

Item no. 52489-5-9970 · ENG · Revision 84865 · Release 2015-01-27 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com