Operating instructions – ebm-papst R3G310-AX54-21 User Manual

Page 9

background image

Operating instructions

R3G310-AX54-21

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

KL1

1

L1

Mains supply connection, supply voltage 1~200-277 V AC; 50/60 Hz

KL1

2

N

Mains supply connection, supply voltage 1~200-277 V AC; 50/60 Hz

PE

PE

Earth connection, PE connection

KL2

1

NO

Status relay, floating status contact; option 1: close with error; option 2: close with run monitor error message

KL2

2

COM

Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA

KL2

3

NC

Status relay, floating status contact; option 1: break with error; option 2: break with error for run monitor error
message

KL3

1

RSA

Bus connection RS485; RSA; MODBUS RTU

KL3

2

RSB

Bus connection RS485; RSB; MODBUS RTU

KL3

3

GND

Signal ground for control interface

KL3

4

Ain1 U

Analog input 1 (set value); 0-10 V; Ri= 100kOhm; parametrisable curve; only usable as alternative to input
Ain1 I

KL3

5

+10 V

Fixed voltage output 10 VDC; + 10 V +/-3%; max. 10 mA; short circuit proof; power supply for ext. devices
(e.g. potentiometer)

KL3

6

Ain1 I

Analog input 1 (set value); 4-20 mA; Ri= 100 Ohm; parametrisable curve; only usable as alternative to input
Ain1 U

KL3

7

Din1

Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridge to
GND or applied voltage < 0.8 VDC; reset function: triggers software reset after a level change to <0.8 V

KL3

8

Din2

Digital input 2: parameter set switch 1/2; according to EEPROM setting, the valid/used parameter set is
selectable per BUS or per digital input DIN2. Parameter set 1: open pin or applied voltage 5 to 50 VDC;
parameter set 2: bridge to GND or applied voltage < 0.8 VDC

KL3

9

Din3

Digital input 3: control characteristic of the integrated controller; according to EEPROM setting, the control
characteristic of the integrated controller is normally/inversely selectable per BUS or per digital input; normal:
open pin or applied voltage 5 to 50 VDC; inverse: bridge to GND or applied voltage < 0.8 VDC

KL3

10

GND

Signal ground for control interface

KL3

11

Ain2 U

Analog input 2; actual sensor value 0-10 V; Ri= 100kOhm; parametrisable curve; only usable as alternative to
input Ain2 I

KL3

12

+20 V

Fixed voltage output 20 VDC; + 20V +25/-10%; max. 50 mA; short circuit proof; power supply for ext.
devices (e.g. sensors)

KL3

13

Ain2 I

Analog input 2; actual sensor value 4-20 mA; Ri= 100 Ohm; parametrisable curve; only alternative to input
Ain2 U

KL3

14

Aout

Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/ of
the actual motor speed. Parametrisable curve.

Item no. 50235-5-9970 · ENG · Revision 84593 · Release 2015-01-05 · Page 9 / 12