3.2 Nominal data

Motor

M3G084-GF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

3100

Power input / W

1000

Current draw / A

1.6

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.01

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

61.4

47.5

51.5

Efficiency grade N

71.9

58

62

Power input P

ed

/ kW

0.99

Air flow q

v

/ m³/h

2675

Pressure increase total p

sf

/ Pa

758

Speed n / min

-1

3115

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

11.8 kg

Size

280 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium, coated in black

Material of impeller

Aluminium sheet, white plastic-coated

Material of mounting
plate

Sheet steel, galvanised and coated in
white

Material of support
bracket

Steel, galvanised and coated in black

Material of inlet nozzle

Sheet steel, galvanised and coated in
white

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"B"

Humidity class

F5

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- Alarm relay
- Output limit
- Motor current limit
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer at the connection point of the
housing)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

; Secure the mounting screws against accidentally coming loose (e.g.

by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 51319-5-9970 · ENG · Revision 82513 · Release 2014-08-05 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com