Operating instructions – ebm-papst K3G280-AU06-B6 User Manual
Page 5
Operating instructions
K3G280-AU06-B6
Translation of the original operating instructions
3.2 Nominal data
Motor
M3G084-GF
Phase
1~
Nominal voltage / VAC
230
Nominal voltage
range / VAC
200 .. 277
Frequency / Hz
50/60
Type of data definition
ml
Speed / min
-1
2800
Power input / W
715
Current draw / A
3.1
Min. ambient temperature
/ °C
-25
Max. ambient
temperature
/ °C
40
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category
A
Efficiency category
Static
Variable speed drive
Yes
Specific ratio
*
1.01
*
Specific ratio = 1 + p
fs
/ 100 000 Pa
Actual
Request
2013
Request
2015
Overall efficiency η
es
/ %
58.7
46
50
Efficiency grade N
70.7
58
62
Power input P
ed
/ kW
0.72
Air flow q
v
/ m³/h
2110
Pressure increase total p
sf
/ Pa
667
Speed n / min
-1
2770
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass
11.5 kg
Size
280 mm
Surface of rotor
Coated in black
Material of electronics
housing
Die-cast aluminium, coated in black
Material of impeller
Aluminium sheet, white plastic-coated
Material of mounting
plate
Sheet steel, galvanised and coated in
white
Material of support
bracket
Steel, galvanised and coated in white
Material of inlet nozzle
Sheet steel, galvanised and coated in
white
Number of blades
7
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"B"
Humidity class
F5
Mounting position
Shaft horizontal or rotor on bottom; rotor
on top on request
Condensate discharge
holes
Rotor-side
Operation mode
S1
Motor bearing
Ball bearing
Technical features
- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- Alarm relay
- Motor current limit
- PFC, active
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Electrical leads
Via terminal box
Motor protection
Thermal overload protector (TOP) wired
internally
Protection class
I (if protective earth is connected by
customer at the connection point of the
housing)
Product conforming
to standard
EN 61800-5-1; CE
Approval
EAC
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+80 °C
Min. permissible
ambient motor temp.
(transp./storage)
-40 °C
Item no. 51318-5-9970 · ENG · Revision 82624 · Release 2014-08-29 · Page 5 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com