Operating instructions – ebm-papst D4E180-BA02-02 User Manual
Page 5

Operating instructions
D4E180-BA02-02
Translation of the original operating instructions
3.2 Nominal data
Motor
M4E068-LA
Phase
1~
1~
Nominal voltage / VAC
230
230
Nominal voltage
range / VAC
208 .. 230
208 .. 230
Frequency / Hz
50
60
Type of data definition
fa
fa
Valid for approval /
standard
CE
CE
Speed / min
-1
1300
1360
Power input / W
360
460
Current draw / A
1.58
2.02
Motor capacitor / µF
10
10
Capacitor voltage / VDB
400
400
Min. back pressure / Pa
0
0
Min. ambient temperature
/ °C
-25
-25
Max. ambient
temperature
/ °C
65
40
Starting current / A
3.3
3.1
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category
A
Efficiency category
Static
Variable speed drive
No
Specific ratio
*
1.00
*
Specific ratio = 1 + p
fs
/ 100 000 Pa
Actual
Request
2013
Request
2015
Overall efficiency η
es
/ %
26.9
26.3
33.3
Efficiency grade N
37.6
37
44
Power input P
e
/ kW
0.2
Air flow q
v
/ m³/h
1000
Pressure increase total p
sf
/ Pa
196
Speed n / min
-1
1420
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass
10 kg
Size
180 mm
Surface of rotor
Coated in black
Material of impeller
Sheet steel, hot-galvanised
Housing material
Sheet steel, hot-galvanised
Direction of rotation
Counter-clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"B"
Humidity class
F3-1
Mounting position
Any
Condensate discharge
holes
None
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
< 0.75 mA
Motor protection
Thermal overload protector (TOP) wired
internally
Protection class
I (if protective earth is connected by
customer)
Product conforming
to standard
EN 60335-1; CE
Approval
CCC; GOST
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+ 80 °C
Min. permissible
ambient motor temp.
(transp./storage)
- 40 °C
Item no. 11070-5-9970 · Revision 82891 · Release 2014-04-15 · Page 5 / 9