beautypg.com

Operating instructions – ebm-papst D3G318-AA37-11 User Manual

Page 8

background image

Operating instructions

D3G318-AA37-11

Translation of the original operating instructions

4.4 Connection screen

No.

Conn.

Designation

Colour

Function / assignment

1

1

PE

green/
yellow

Ground wire

1

3

N

blue

Supply voltage, neutral conductor, 50/60 Hz

1

4

L

black

Supply voltage, phase, 50/60 Hz

1

5

COM

white 1

Floating status message contact, normally closed connection (2 A, max. 250 VAC,
min. 10 mA, AC1)

1

6

NC

white 2

Floating status message contact, normally closed connection

2

8

0-10 V

yellow

Control input, set value 0-10 VDC, impedance 100 kΩ, SELV

2

10

P

orange

not assigned

2

11

10 VDC

red

Voltage output 10 VDC (+/-3 %), max. 10 mA, supply voltage for external devices (e.g.
potentiometer), SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no. 50047-5-9970 · ENG · Revision 84593 · Release 2015-01-05 · Page 8 / 11