Vent-free propane/lp pedestal stove, Installation, Continued – Desa Tech S26PT User Manual

Page 8

background image

8

105684

VENT-FREE PROPANE/LP PEDESTAL STOVE

For more information, visit www.desatech.com

Tee
Joint

Pipe
Nipple

Cap

3" Minimum

Sediment
Trap

Gas
Regulator
of Heater

From External
Regulator (11"
W.C.** to 14"
W.C. Pressure)

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

Approved
Flexible Gas
Hose (if allowed
by local codes)

Figure 7 - Gas Connection

* Purchase the optional CSA design-certified equipment shutoff valve from your dealer.

See Accessories, page 22.

** Minimum inlet pressure for purpose of input adjustment.

CAUTION: Avoid damage to

regulator. Hold gas regulator with
wrench when connecting it to gas
piping and/or fittings.

CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

Installation must include an equipment
shutoff valve, union, and plugged 1/8" NPT
tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream
from heater (see Figure 7).

IMPORTANT:

Install equipment shutoff

valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

WARNING: Never connect

heater to private (non-utility) gas
wells. This gas is commonly
known as wellhead gas.

CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

We recommend that you install a sediment
trap in supply line as shown in Figure 7.
Locate sediment trap where it is within
reach for cleaning. Install in piping system
between fuel supply and heater. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

INSTALLATION

Continued

CONNECTING TO GAS
SUPPLY

WARNING: A qualified service

person must connect heater to gas
supply. Follow all local codes.

Installation Items Needed

Before installing heater, make sure you have
the items listed below.

• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench

* An CSA design-certified equipment
shutoff valve with 1/8" NPT tap is an ac-
ceptable alternative to test gauge connec-
tion. Purchase the optional CSA design-
certified equipment shutoff valve from your
dealer. See Accessories, page 22.

Figure 5 - Gas Regulator Location and
Gas Line Access Into Stove Cabinet

Front
of
Stove
Unit

Gas Regulator
Inlet Connection

Back View

Side View

CAUTION: Never connect

heater directly to the propane/LP
supply. This heater requires an ex-
ternal regulator (not supplied). In-
stall the external regulator between
the heater and propane/LP supply.

Figure 6 - External Regulator With Vent
Pointing Down

Propane/LP
Supply Tank

External
Regulator

Vent
Pointing
Down

The installer must supply an external regulator.
The external regulator will reduce incoming
gas pressure. You must reduce incoming gas
pressure to between 11 and 14 inches of water.
If you do not reduce incoming gas pressure,
heater regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 6. Pointing the vent down
protects it from freezing rain or sleet.