beautypg.com

Honeywell R841E User Manual

Honeywell Radiators

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HONEYWELL I

T R A D E L I N E

I CONTROLS

application

The R841E Electric Heating Relay is a two-switch

device used with either one 24-volt, two-wire thermo­
stat to control one or two loads simultaneously; or
with two thermostats to control two independent loads.

It is a direct following relay which operates with each

cycle of the thermostat (4 to 6 cycles per hour with a

T822Dor T87F Thermostat), It has an integral trans­

former. The R841E should not be used as a discon­

nect switch.

2.

Run line-voltage wire from heaters to relay

junction box. Using solderless connectors, make the

connections shown in Figs, 3, 4, or 5.

3.

Run thermostat cable from the thermostat to the

relay. Connect to relay according to Figs, 3, 4 or 5.

ALL WIRING MUST AGREE WITH LOCAL CODES.

Be sure the power supply voltage agrees with the rat­
ing on the relay label.

INSTALLATION-

OPERATION

The R841E must be mounted where the ambient tem­

perature is within the range of -20 to ISO F the year

around. The small size and silent operation of the

R841 allow installation in a living area, utility room
or basement. The bimetal-operated switches permit
mounting the relay in any convenient position.

Fig. 1—Typical installation of relay in baseboard

heater.

The cycling pattern of the R841E is determined by

the thermostat. On a call for heat, the thermostat
activates one or both of the low voltage resistance
heaters in the R841E. The heater drives a bimetal
that actuates the spst MICRO SWITCH* snap acting
switch. The bimetal is ambient-temperature compen­
sated between -20 and 150 F. At rated voltage and
frequency, the R841E switch contacts''make''approx­
imately 80 seconds (from cold start) after the thermo­
stat calls for heat and break about 100 seconds after
the thermostat stops calling for heat.

Fig. 1 shows a typical installation within a com­

partment enclosure on the end of a baseboard heater.

In this application the conduit bushing can be connect­
ed to the wiring compartment in the heater. The back
of the compartment enclosure should be equipped with
embossings to clear mounting screws.

The R841E may also be mounted without compart­

ment enclosure on a wireway or junction box (Fig. 2).

CAUTION: DISCONNECT POWER SUPPLY.

1.

Fasten relay securely to mounting surface using

the two mounting holes in the taackplate, or the con­

duit bushing.

♦Trademark
5-68

J. C.

Fig. 2—Four relays mounted on wireway.

CHECKOUT-

After mounting and wiring have been completed,

turn on the power supply. Set the thermostat above
room temperature until the electric heating equipment
starts (allow about 80 seconds from cold start). Per­

mit the system to operate long enough to prove the

heating equipment functions properly. Return the
thermostat to the desired room temperature before
leaving the installation.

Fofrn Numbiir

93—6804

Rasidential Div.

Table of contents