Battery mode – CyberPower Systems OR1500ELCDRM1U User Manual

Page 2

background image














DEFINITIONS FOR ILLUMINATED LCD INDICATORS







Line mode

UPS Status Display

Capacity

Display

Digital Value Display

Select SW

Press

Load

Cap.

Battery

Cap.

Input

Voltage

Output

Voltage

Run

Time

% of

Load

% of

Batt.

Initial

V X -- X V X

V

1st

V X -- X V X

V

2nd

V X -- X V X

V

3rd

V X -- X X V

V

4th

V X -- X V X

V

5th(Return)

V X -- X V X

V

Press >3sec

(Sound

Disable)

V X V X -- --

--

--

-- -- --

Press >3sec

again(Sound

Enable)

V X X X -- --

--

--

-- -- --

(Overload)

V X -- V -- --

--

--

-- -- --

"V" : Illuminated,

"X" : Not Illuminated, "--" : Either


Battery mode

UPS Status Display

Capacity

Display

Digital Value Display

Select SW

Press

Load

Cap.

Battery

Cap.

Input

Voltage

Output

Voltage

Run

Time

% of

Load

% of

Batt.

Initial X

V

--

X

V

X V

1st X

V

--

X

V

X

V

2nd X

V

--

X

V

X

V

3rd X

V

--

X

X

V

V

4th X

V

--

X

V

X

V

5th(Return) X

V

--

X

V

X

V

Press >3sec

(Sound

Disable)

X V V X -- --

--

--

-- -- --

Press >3sec

again(Sound

Enable)

X V X X -- --

--

--

-- -- --

(Overload) X V -- V --

--

--

--

--

--

--

"V" : Illuminated,

"X" : Not Illuminated, "--" : Either



TROUBLE SHOOTING

Problem

Possible Cause

Solution

Full-time surge
protection outlets
stop providing
power to
equipment.

Circuit breaker has tripped
due to an overload.

Turn the UPS off and unplug at least one
piece of equipment. Wait 10 seconds,
reset the circuit breaker by depressing the
button, and then turn the UPS on.

Battery not fully charged.

Recharge the battery by leaving the UPS
plugged in.

The UPS does
not provide
expected
runtime.

Battery is slightly worn out.

Contact CyberPower Systems about
replacement batteries at
[email protected]

The on/off switch is
designed to prevent
damage by rapidly turning it
off and on.

Turn the UPS off. Wait 10 seconds and
then turn the UPS on.

The battery is worn out.

Contact CyberPower Systems about
replacement batteries at
[email protected]

The UPS will not
turn on.

Mechanical problem.

Contact CyberPower Systems at
[email protected]

The USB cable is not
connected.

Connect the USB cable to the UPS unit
and an open USB port on the back of the
computer.

PowerPanel

®

Business Edition

is inactive.

The unit is not providing
battery power.

Shutdown your computer and turn the
UPS off. Wait 10 seconds and turn the
UPS on. This should reset the unit.

Additional troubleshooting information can be found at eu.cyberpowersystems.com

TECHNICAL SPECIFICATIONS

Model

OR1000ELCDRM1U OR1500ELCDRM1U

Capacity (VA)

1000VA/600W

1500VA/900W

Input

Input Voltage Range

160VAC~270VAC

Frequency Range

50/60Hz (Auto Sensing)

AVR Function

Boost Only

Output

On Battery Output
Voltage

230Vac +/-10%

On Battery Output
Frequency

50/60Hz +/-1%

Transfer Time

4ms Typical

Overload Protection

On Utility: Circuit Breaker, On Battery: Internal Current Limiting

Surge Protection

Lightning / Surge
Protection

Yes

Network/ Phone/ Fax/
Modem Protection

RJ11/RJ45 ( One In/ One Out )

Operating Temperature

+32

°F to 104°F ( 0°C to 40°C )

Physical

Total # of UPS outlets

IEC320 C 13 x 6 ( Backup x 4 )

Maximum
Dimensions(cm)

1U Rack 43.3 x 38.9 x 4.4

1U Rack 43.3 x 48.5 x 4.4

Weight (kg)

16.1

19.4

Battery

Sealed Maintenance
Free Lead Acid Battery

6V / 7Ah x4

6V / 9Ah x4

Typical Recharge Time

8 hours

Charging Current(Max.)

1A

User Replaceable

Yes

Status Indicators
Indicators

Power On, Wiring Fault, LCD Display

Audible Alarms

On Battery, Low Battery, Overload

Communication

PowerPanel

®

Business

Edition Software

Windows 2000/NT/XP/Vista,Mac OSX,Linux

Management

Self -Test

Yes

Auto-Charger Yes
Auto-Restart Yes
USB interface

Yes

Dry contact Closure

Yes

SNMP/HTTP
Networking

Optional

CYBERPOWER GREENPOWER UPS TECHNOLOGY

Our new UPS circuit is designed to save energy operating in GreenPower

Bypass Mode.

A traditional UPS circuit with AVR provides normal output voltage through the

Relay and AVR transformer. The current travels first through the transformer

conducting energy and generating heat. This heat creates energy dissipation

resulting in a "Power Loss" or consumption of utility power and money.

CyberPower's GreenPower Circuit Design is a solution to this "Power Loss." When the Utility Power is

operating normally, our Green Power UPS works in Bypass Mode. Our GreenPower design conducts

power only through the Relay and still provides normal output voltage. Bypassing the transformer

reduces power consumption thereby conserving energy and saving money. When the utility power is

abnormal the UPS will operate under Battery or AVR Mode. Under this condition Green Power UPS and

a traditional UPS would operate about the same.

On average utility power operates 88% of the time and the CyberPower GreenPower Technology will

work in its money/energy saving Bypass Mode.

For more information, visit eu.cyberpowersystems.com or contact

CyberPower Systems B.V.

Flight Forum 3545 5657DW Eindhoven The Netherlands

Tel: +31 40 2348170, E-MAIL: [email protected]

CyberPower Systems Inc. (USA) 4241 12th Avenue East, Suite 400, Shakopee, MN 55379, U.S.A.

Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: [email protected]

Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole

or in part without permission is prohibited. PowerPanel

®

and PowerPanel

®

Plus are trademarks of

CyberPower Systems (USA) Inc.

4. Remove the retaining screw of
the cable connectors.

5. Replace the new battery pack. Assemble
the screws, cover, cable and front panel in
the reverse sequence of above steps.
Recharge the unit for 4-8 hours to ensure
the UPS performs expected runtime