beautypg.com

7 | maintenance – GEA Bock HGX34 CO2 T User Manual

Page 33

background image

D
GB
F
E

33

96156-12.2014-DGb

Available accessories can be found on the Internet at www.gea.com.

7.4 Accessories

7.2 Work to be carried out
In order to guarantee optimum operational reliability and service life of the compressor,

we recommend

carrying out servicing and inspection work at regular intervals:

Oil change:

-

not mandatory for factory-produced series systems.

-

for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.

Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.

Only use genuine GEA Bock spare parts!

7.3 Spare part recommendation

7.5 Decommissioning

7| Maintenance

Close the shut-off valves on the compressor. CO

2

does not need to be recycled and can therefore

be blown off into the environment. It is essential to ensure good ventilation or conduct the CO

2

into

the outdoors to avoid danger of suffocation. When releasing CO

2

, avoid a fast drop in pressure to

prevent oil from exiting with it. If the compressor is unpressurized, remove the piping on the pressure-
and suction-side (e.g. dismantling of the shut-off valve, etc.) and remove the compressor using an
appropriate hoist. Dispose of the oil inside in accordance with the applicable national regulations.
When decommissioning the compressor (eg. for service or replacement of the compressor) larger
amounts of CO

2

in the oil can be set free. If the decompression of the compressor is not sufficient

enough, closed shut-off valves may lead to intolerable excessive pressure. For this reason the
suction side (LP) and the high pressure side (HP) of the compressor have to be secured by
decompression valves.

HGX34 / ... CO

2

T

110-4

130-4
150-4

170-4
190-4

210-4

230-4

290-4

Designation

Ref. No.

Ref. No.

Ref. No.

Ref. No.

Ref. No.

Set of gaskets until AS 036

80911

80910

80909

80908

--

Set of gaskets from AS 037

81178

81179

81180

81181

81182

Set of valve plate kit until AS 036

80758

80759

80760

80761

--

Set of valve plate kit from AS 037

81173

81174

81175

81176

81177

Set oil pump kit

80774

Set

oil sump heater

, 230 V AC

80854