Blue Sky Energy - Solar Boost 2512i and 2512iX
9
IPN NETWORK WIRING
FIGURE 5
IPN Network Address – DIP’s #1, #2 & Jumper A2 (Omitted on SB2512i)
¾
A single controller must be set to IPN network address 0 (zero). In a multi-controller system one controller must be set to
address 0 (zero) to serve as the master. The other controllers must be set to address 1-7 with no two controllers set the same.
The SB2512iX requires that a jumper be soldered across location A2 to select addresses 4 through 7.
IPN NETWORK ADDRESS
MASTER
SLAVES
DIP
SWITCH
0
1
2
3
4
5
6
7
JUMPER
(A2) NO NO NO NO YES YES YES YES
# 1 (A1)
OFF
OFF
ON
ON
OFF
OFF
ON
ON
# 2 (A0)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
MOUNTING
¾
CAUTION: Mount the 2512 vertically to promote air flow and do not enclose in a confined space. The 2512 is not watertight and
must be protected from rain, snow and excessive moisture. Take care not to place mounting screws under large brown capacitor
when securing mounting box to mounting surface. DO NOT remove from or install into mounting box with power applied as damage
resulting from shorting to the mounting box voids the limited warranty. Optional black powder coated deluxe mounting box available.
DETAILED DIMENSIONAL DRAWING
FIGURE 6
)