Blue Sky Solar Boost 3024Di User Manual
Page 2
Network connection and power for the display are provided by the Solar Boost 3024i using the short telephone cable supplied. The
cable should connect between the IPN Display connector on the Solar Boost 3024i main circuit board and the IPN Network connector
on the display circuit board.
¾
Note that standard 4-pin telephone cables swap pin numbers end-to-end. This end-to-end pin swap is
required for the display to operate properly. If cables are custom terminated or cable couplers are used,
be certain the pin swap is maintained as shown below.
Troubleshooting Guide
SYMPTOM
PROBABLE CAUSE
ITEMS TO EXAMINE OR CORRECT
Completely dead, no
display
No power
Charge controller not properly powered
Cable faulty, not plugged in or cable pins do not swap
Display turns on, but
battery voltage displays
“– – –“ rather than a
number
Display not communicating with
charge controller
Cable faulty
One charge controller is not set to be Master, or more than
one charge controller is set to be Master
One or more charge controllers on network has open Bat –
connection preventing communication
When charger turns on,
output current displays
“– – –“ rather than a
number
Output current display selection
set for an address not present on
the IPN network
Configure display IPN network address DIP switch to properly
read output current of a charger present on the IPN network
When charger turns on,
output current displays
but the value seems
incorrect
Output current display selection
set for wrong IPN network
address
Bat– connected to PV– outside
charge controller
Configure display IPN network address DIP switch to properly
read output current of a charger present on the IPN network
Some charge controllers require Bat– not be connected to PV–
outside charge controller, see charge controller manual.
Voltage or current value
seems to be stuck and
does not change
Display or charge controller IPN
network addressed changed
Display lost communication link
with charge controller
Configure display IPN network address DIP switch to properly
read output current of a charger present on the IPN network
Intermittent faulty display cable