Extending the interconnecting medium or backbone, 2 features, 3 specifications – Contemporary Research TD960801-0MC User Manual
Page 6: Electrical, Power options
TD960801-0MC
2
Extending the Interconnecting Medium or Backbone
The backbone side of the EXTEND-A-BUS must comply with
standard ARCNET cabling rules. Companion AI ARCNET
active hubs are available for extending the backbone cabling up
to 6 km using coaxial cabling and ten active hubs. When using
a fiber optic backbone, a maximum of 4.8 km can be achieved
requiring two active hubs. Hubs are cascaded to reach the
required distance.
1.2
Features
•
Extends the length of DeviceNet networks up to 6 km
•
Fully DeviceNet compliant
•
Fiber optic or coaxial cabling
•
Star, bus or distributed star topology
•
Variable data rate up to 500 kbps
•
Low voltage AC or DC powered
•
Panel-mount enclosure
1.3
Specifications
Electrical
DC
AC
Input voltage:
10–36 volts
8–24 volts
Input power:
4 watts
4VA
Input frequency:
N/A
47-63 Hz
Power Options
– DC powered
– Redundant powered
– AC powered
– AC powered with battery backup