Problem analysis:

1. Data communication unsuccessful

A. Check RS-232 interfaces whether to be correct;

B. Check RS-485 interfaces whether to be correct;

C. Check whether RS-232 signal level(TXD、DTR、RTS) lower than+5V,

if that, it can get through power from 6

th

pin of DB9 Male.

2. Data missing or messy code

A. Check whether the baud rate and format of both sides of data

communication equipment are same.

B. If possible, add the matched resistance on the terminal circuit (120 Ω,1/4

w)

B. RS-232/RS-422 communicate as point to point s four wire, asynchronous,

full-duplex method, this method is mainly used for con trol-side equipment

connector is RS-232, and the connector of equipment un der control is

RS-422,and it will connect many RS -422 devices. From device (RS -422

SLAVE) MAX connection is 32~128 RS -422 devices. In order to avoid signal

reflex and interfering signal, it should be add the matched resistance on the

terminal circuit (120Ω, 1/4 w)

(2) When the HXSP-2108C connects as RS-232/RS-4485, the device

connects as RS-485 connection method.

A. RS-232/RS-485 communicate as point to point two wire , half-duplex

method, this method is mainly used for control -side equipment connector is

RS-232, and the connector of equipment un der control is RS-485, The two

side can not communicate directly because of disaccord of two side electrical

specialty, HXSP-2108C converter can be used for transparent change the

RS-232 signals to RS-485 signals, and it need not RTS.

B. RS-232/RS-485 communicate as point to points two wire , half-duplex

method, this method is mainly used for control -side equipment connector is

RS-232, and the connector of equipment un der control is RS-485,and it will

connect many RS-485 devices. From device (RS -485 SLAVE) MAX

connection is 32~128 RS-485 devices. In order to avoid signal reflex and

interfering signal, it should be add the matched resistance on the terminal

circuit (120Ω, 1/4 w)

Power Supply and Surge Protection

1. HXSP-2108C converter can get the power from the 9V adapter or from other

DC power or device. Power supply voltage should be +9V, electric should be

100mA.

2 . Surging protection

Ordinary interface converters do not provide large energy protection

equipment, and they try to release the energy to the Earth through the smallest

resistance route for the transient high voltage in the interface data line of wire

sensor. So it is easy to make the interface component’s damage. Interface

Converters during the process should avoid grounding vacant in order to

ensure the safety of use and reliable communi cations.