Wine-Mate SSLWC Series User Manual
Page 22
- 21 -
Model No
Equivalent
Line Set
Liquid Line
Suction Line
Drain Line
Recommended
Charge
WM-2500SSLWC
<= 75 FT
1/4" OD
3/8” OD
1/2” OD
R134a/19 OZ
WM-4500SSLWC
<= 75 FT
1/4" OD
1/2” OD
1/2” OD
R134a/26 OZ
WM-6500SSLWC
<= 75 FT
1/4" OD
1/2” OD
1/2” OD
R134a/32 OZ
7. Water Piping
If a water pump is used, install it before the water inlet so that the condenser
cooling water is fed from the discharge side of the pump.
Model No
Condensing Unit
Water Flow
(75°F inlet, gal/min)
Water-in
Connection
Water-out
Connection
Water Pressure
Drop (PSI)
WM-2500SSLWC
WM-250SCU-WC
0.2
3/8” FPT
1/2" ODF SOLDER
0.2
WM-4500SSLWC
WM-450SCU-WC
0.4
3/8” FPT
1/2" ODF SOLDER
0.2
WM-6500SSLWC
WM-650SCU-WC
0.6
3/8” FPT
1/2" ODF SOLDER
0.2
8. Connecting Electrical Wires
Connect all electrical components using the wiring diagrams in accordance with
all state and local codes.
9. Evacuating, Charging and Starting the system
CAUTION:
• Always use the superheat and subcooling, pressure readings to charge
refrigerant properly; the listed charge amounts are used for reference
only.
1) Evacuate the system; both discharge and suction valves must be in the
middle positions during evacuating.
2) Charge the system through both suction and discharge valves with refrigerant
using the recommended initial amount; both discharge and suction valves
must be in the middle positions during charging.
3) Turn on the water valve.
4) Turn on the power to start the system and check the following temperatures
and pressures.
10. Adjusting and Completing the installation
1) Set the water regulating valve opening set-point at refrigerant pressure of 120
PSIG. Turn counterclockwise to raise the operating set-point.