CellarPro 1800XTS-B BEER COOLING UNIT, 2176 User Manual
Page 21

Power On/Off Button
Press “Power On/Off” to turn the unit on and off
When the “Compressor On” indicator light is on, the
Compressor is running. When the “Fan On”
indicator light is on, the Fan is running
Up and Down Buttons
To view the “High Temp” recorded by the cooling
unit, press the “Up” button once.
To view the “Low Temp” recorded by the cooling
unit, press the “Down” button once
To reset the “High Temp” or “Low Temp”, press the
“Set” button for three seconds while “Hi” or “Lo” is
displayed. “RST” will blink three times to indicate
confirmation.
Set Button
The cooling unit is factory preset with a Minimum Set
Point of 58°F and a Temperature Differential of 4°F.
This means that the cooling unit will turn on when
the display rises above 62°F (58°F + 4°F), and turn off
when the display falls below 58°F. In this example,
the average temperature inside the cellar will be
60°F.
To view the Minimum Set Point, press the “Set”
button for one second.
To change the Minimum Set Point,
1. Press the “Set” button for three seconds until “°F”
blinks
2. Press the “Up” or “Down” button
3. Press the “Set” button to confirm
The “Set” temperature will blink three times to
indicate confirmation.
The recommended Minimum Set Point range is 53 -
60°F. To change the Temperature Differential, see
“Advanced Operation” later in this chapter.