BATTERY REPLACEMENT PROCEDURE:


For UP500E/UP750E only



































STORAGE

First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables

connected the UPS to avoid battery drain. To store your UPS for an extended period, cover it and

store with the battery fully charged. Recharge the battery every three months to insure battery life. If

the battery remains uncharged for an extended period of time, it may suffer permanent loss of

capacity.

TROUBLE SHOOTING

Problem

Possible Cause

Solution

Batteries are not fully charged.

Recharge the battery by leaving the UPS
plugged in.

The UPS does not
perform expected
runtime.

Battery is slightly worn out.

Contact CyberPower Systems at

[email protected]

The on/off switch is designed to
prevent damage by rapidly
turning it off and on.

Turn the UPS off. Wait 10 seconds and then
turn the UPS on.

The unit is not connected to an
AC outlet.

The unit must be connected to a 220-240V
50/60Hz outlet.

The battery is worn out.

Contact CyberPower Systems at

[email protected]

The UPS will not
turn on.

Mechanical problem.

Contact CyberPower Systems at

[email protected]

Fuse is blown due to overload

Turn the UPS off and unplug at least one piece
connected equipment. Unplug the power cord of
the UPS then remove the fuse compartment
beneath the power inlet of the UPS and replace
the blown fuse with a spare one. Lock the
compartment back to the UPS. Connect power
cord then turn the UPS on. Make sure that your
spare fuse meets the specification: 6.3A, 250V,
5x10mm.

Batteries are discharged

Allow the unit to recharge for at least 4 hours.

Outlets do not
provide power to
equipment

Unit has been damaged by a
surge or spike.

Contact CyberPower Systems at

[email protected]

The serial cable is not
connected.

Connect the serial cable to the UPS unit and
an open serial port on the back of the
computer. You must use the cable that came
with the unit.

The serial cable is connected to
the wrong port.

Try another serial port of your computer.

The unit is not providing battery
power.

Shutdown your computer and turn the UPS off.
Wait 10 seconds and turn the UPS back on.
This should reset the unit.

PowerPanel

®

is

inactive (all icons
are gray).

The serial cable is not the cable
that was provided with the unit.

You must use the cable included with the unit
for the software.

TECHNICAL SPECIFICATIONS

Model

UP350TE

UP500TE

UP500E UP750E

Capacity (VA)

350VA

500VA

500VA

750VA

Capacity (Watts)

210W

300W

325W

450W

Input

Input Voltage Range

220-240Vac

Frequency Range

50/60 Hz

Output

On Battery Output

Voltage

Simulated Sine Wave at 230Vac +/- 7%

On Battery Output

Frequency

50/60 Hz

Overload Protection

On Utility: Fuse, On Battery: Internal Current Limiting

Surge Protection and Filtering

Lightning / Surge

Protection

Yes

Network Protection

RJ45 (One In/One Out)

Physical

Total # of UPS

Receptacles

2 2

Maximum Dimensions

23.8cm*8.0cm*13.7cm 28.3cm*9.1cm*16.4cm

Weight (Kg)

4.4

5.0

6.4

7.5

Battery

Sealed Maintenance

Free Lead Acid

Battery

12V / 4AHx1

12V / 4.5AHx1

12V / 7AH x1

12V / 9AH x1

User Replaceable

N/A

Yes, Hot Swappable Battery Pack

Typical Recharge

Time

8 Hours

Warning Diagnostics

Indicators

Power On, Using Battery, Boost, Buck

Audible Alarms

On Battery, Low Battery, Overload

Environmental

Operating

Temperature

+32

°F to 95°F ( 0°C to 35°C )

Operating Relative

Humidity

0 to 95% NON-CONDENSING

Communication

PowerPanel

®

Software

Windows 98/ME/2000/NT/XP, Server 2003

Management

Auto-Charger Yes

Auto-Restart Yes

1. Remove the 2 retaining screws then push

the battery cover backward and remove the
cover.

2. Lean the UPS to one side and pull out the

battery partially from the compartment.
Disconnect the battery wires from the
battery, and then remove the battery from
the compartment.

3. Install the replacement battery by connecting

the red wire to the positive (+) terminal of the
battery and connecting the black wire to the
negative (-) terminal of the battery.

4. Slide the battery back into the

compartment. Turn the UPS upside
down to help the batteries entirely slide
into the compartment. Replace the cover
and the retaining screws.


REMINDER
: Recharge the unit for 4 – 8
hours to ensure the UPS performs
expected runtime

DEFINITIONS FOR ILLUMINATED LED INDICATORS



Power On



Using

Battery


Fuse




Alarm

Condition

On

Off Normal Off

Normal

Off On

Normal

Two

Beeps

Utility Failure- The UPS is providing battery
power to the Battery-Power Supplied outlets.

Off On

Normal

Rapid

Beeps

Utility Failure- The UPS is providing battery
power. The rapid beeps indicate the battery will
run out of charge within a few minutes.

Off On/Off

Blown

Two beeps

or rapid

beeps

Overload- Occurs in the Full-time Surge
Protection Outlets. Please turn the UPS off and
unplug at least one piece of equipment from the
UPS. Replace the fuse with a spare one then
turn the UPS on.

Off On/Off

Normal/

Blown

Long Beep

Overload- Occurs in the Battery-power Supplied
Outlets. Turn the UPS off and unplug at least
one piece of equipment from the UPS. Check
the fuse and do the replacement if necessary.
Turn the UPS on.

For more information, visit

eu.cyberpowersystems.com

or contact

CyberPower Systems B.V.

Flight Forum 3545, 5657DW Eindhoven, The Netherlands

TEL: +31 (0)40 2348170, FAX: +31 (0)40 2340314, E-MAIL:

[email protected]

CyberPower Systems Inc. (USA)

4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A.

Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL:

[email protected]

Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in

whole or in part without permission is prohibited. PowerPanel

®

and PowerPanel

®

Plus are

trademarks of CyberPower Systems (USA) Inc.

CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects

in design, assembly, materials and workmanship for two years ( battery is only one year) from the

date of original purchase. Any warranty services, please contact your local dealers or distributors.