FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters.

All applications of these furnaces require the use of field
installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabi-
net. DO NOT attempt to install any filters inside the furnace.

NOTE: Single side return above 1800 CFM is approved as
long as the filter velocity does not exceed filter manufac-
turer’s recommendation and a transition is used to allow use
on a 20x25 filter.

NOTES:

1. Air velocity through throwaway type filters may not exceed 300

feet per minute (91.4 m/min). All velocities over this require the
use of high velocity filters.

2. Do not exceed 1800 CFM using a single side return and a 16x25

filter. For CFM greater than 1800, you may use two side returns or
one side and the bottom or one return with a transition to allow
use of a 20x25 filter.

* - 24" clearance in front and 18" on side recommended for service access.
All furnaces approved for alcove and attic installation.

ACCESSORIES

PROPANE (LP) CONVERSION KIT -

S1-1NP0347 - All Models except 130K Model
S1-1NP0501 - 130K Model

This accessory conversion kit may be used to convert natural
gas (N) units for propane (LP) operation.

CONCENTRIC VENT TERMINATION -

S1-1CT0302 (2")

S1-1CT0303 (3")

For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Elimi-
nates unslightly elbows for a cleaner installation.

SIDEWALL VENT TERMINATION KIT -
S1-1HT0901 (3")
S1-1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.

CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for instal-
lation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).

SIDE RETURN FILTER RACKS -

S1-1SR0200 - All Models
S1-1SR0402 - All Models
S1-1SF0101 - All Models (Upflow Only)

BOTTOM RETURN FILTER RACKS -

S1-1BR0514 or 1BR0614 - For 14-1/2” cabinets
S1-1BR0517 or 1BR0617 - For 17-1/2” cabinets
S1-1BR0521 or 1BR0621 - For 21” cabinets
S1-1BR0524 or 1BR0624 - For 24-1/2” cabinets

1BR05xx series are galvanized steel filter racks. 1BR06xx
are pre-painted steel filter racks to match the appearance of
the furnace cabinet.

COMBUSTIBLE FLOOR BASE KIT -

For installation of these furnaces in downflow applications
directly onto combustible flooring material, These kits are
required to prevent potential overheating situations.tible floor
base kit provides access for combustible airflow.
S1-1CB0514 - For 14-1/2” cabinets
S1-1CB0517 - For 17-1/2” cabinets
S1-1CB0521 - For 21” cabinets

S1-1CB0524 - For 24-1/2” cabinets

EAC TRANSITION KITS -

For installation of EAC accessories with these furnaces to
provide easy transition of return airflow through the EAC to
get the proper sealing and reduced airflow leakage.

S1-1TK1001 - For all models using side return
S1-1TK1014 - For 14-1/2” cabinets using bottom return
S1-1TK1017 - For 17-1/2” cabinets using bottom return
S1-1TK1021 - For 21” cabinets using bottom return
S1-1TK1024 - For 24-1/2” cabinets using bottom return

HIGH ALTITUDE PRESSURE SWITCHES -

For installation where the altitude is less than 5,000 feet it is
not required that the pressure switch be changed. For alti-
tudes above 5,000 feet, see kits below.
S1-1PS3306 - 040, 080

S1-1PS3307 - 060

S1-1PS3302 - 100, 120, 130

ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.

1H/1C, manual change-over electronic non-programmable
thermostat.

1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

* For the most current accessory information, refer to the
price book or consult factory.

Recommended Filter Sizes (High velocity 600 FPM)

CFM

Cabinet

Size

Side

(in)

Bottom

(in)

800

A

16 x 25

14 x 25

1000

A

16 x 25

14 x 25

1200

A

16 x 25

14 x 25

1200

B

16 x 25

16 x 25

1600

B

16 x 25

16 x 25

1600

C

16 x 25

20 x 25

2000

C

(2) 16 x 25

20 x 25

2200

C

(2) 16 x 25

20 x 25

2000

D

(2) 16 x 25

22 x 25

Unit Clearances to Combustibles

Application

Upflow

Downflow

Horizontal

Top

1" 0" 0"

Vent

0" 0" 0"

Rear

0" 0" 0"

Side

0" 0" 1"

Front*

0" 0" 0"

Floor

Combustible

Combustible

1

1. For combustible floors only when used with special sub-base.

Combustible

Closet

Yes

Yes

Yes

Line Contact

No

No

Yes