Wiring diagrams, Figure r, Figure q – Chromalox PF479-6 User Manual

Page 8: Figure s, Figure t, Figure u, Figure v, Figure w, Figure x

background image

9

WIRING DIAGRAMS

Field Installed

Built-in Or Field Installed
Factory Wiring

Stage 2

Elements

Motor

Stage 1

Elements

Contactor

C1

C2

T1T2T3

T1T2T3

Fuses KTK-3

Fuses

(When Req'd)

BL1

BL2

BL3

L2

L1

L3

3 Phase

60 HZ Power

AL1

AL2 AL3

34-43, 35-43 34-45, 35-45

Fan Relay

C3

Optional Disconnect
Switch Built-in Or
Field Installed

Not For Use With 480V

Cutouts

C1

Optional Thermostat
Built-in Or
Field Installed

Contactor

C2

C3

1

2

3

8

9

7

10 11
12

Summer Fan Switch

Motor

C1

T1T2T3

C2

T1T2T3

Contactor

C2

Standard Motor Connection

Figure R

L1

Contactor

(Typ.)

Fuses

(When Req'd)

AL3

AL2

AL1

BL1

BL2

BL3

Optional Summer
Fan Switch
Built-in Or
Field Installed

Stage 2

Elements

Motor

Cutouts

Note: Heater Requires
Fan Relay For 480V Motors
(See Fig. R)

Optional Disconnect
Switch Built-in Or
Field Installed

34-41 34-42 34-44

C1

T3

T2

T1

L2 L3

1

2

3

8

9

7

10

11

12

Stage 1

Elements

Motor

3 Phase,

60 HZ Power

Optional Thermostat
Built-in Or
Field Installed

C1

T1 T2

T3

C2

T1 T2

T3

To Elements

Stage 1

To Elements

Stage 2

Standard Motor Connection

Fuses

KTK-3

C2

T3

T2

T1

Field Wiring
Built-in Or Field Installed
Factory Wiring

Figure Q

Field Installed
Built-in Or Field Installed
Factory Wiring

Transformer

Color Code Index

Stage 2

Elements

MOTOR

Stage 1

Elements

Contactors

C1

C2

T1T2T3

T1T2T3

C3

C2

C1

X1

X2

H2

H1

Contactor

Cutouts

XFMR

Fan

Stage 1

Stage 2

2 Stage Thermostat
(By Others)

Fuses KTK-3

Fuses

(When Req'd)

BL1

BL2

BL3

L2

L1

L3

3 Phase

60 Hz Power

AL1

AL2 AL3

Disconnect
Switch Built-in Or
Field Installed

32-00 30-00

PRI.
VOLT.

PRI. XFMR

LEAD CLRS.

120V SEC.

LEAD CLRS.

24V SEC.

LEAD CLRS.

208

240

480

H1

BLK

BLK

BLK

H2

RED

ORG

BLK/RED

X1

BLK

BLK

BLK

X2

WHT

WHT

WHT

X1

YEL

YEL

YEL

X2

BLU

BLU

BLU

Warning - First Stage Of
Thermostat Must Be
Connected To Terminals C1
& C2 To Insure That Motor
Will Be Energized With First
Stage Heat Operation

Note: For Single Stage
Thermostat, See Fig. J

Figure S

Field Installed
Built-in Or Field Installed

Factory Wiring

Transformer

Color Code Index

Stage 2

Elements

Motor

Stage 1

Elements

C1

C2

T1T2T3

T1 T2T3

C3

C2

C1

X1

X2

H2

H1

Contactor

(Typ.)

XFMR

Stage 1

Fuses

(When Req'd)

BL1

BL2

BL3

3 Phase

60 HZ Power

AL1

AL2 AL3

Disconnect
Switch Built-in Or
Field Installed

30-43 32-43

C4

C3

Heat

Fan

Stage 2

L1 L2 L3

Fuses KTK-3

2 PDT Switch

(By Others)

2 Stage Thermostat
(By Others)

Cutouts

C1
C4
C2
C3

4

2

1

3

Jumper

Fan

Heat

Thermostat

Jumpers

Thermostat

W/sub-base

(By Others)

Alternate Customer Hook Up (1 Stage)

PRI.
VOLT.

PRI. XFMR

LEAD CLRS.

120V SEC.

LEAD CLRS.

24V SEC.

LEAD CLRS.

208

240

480

H1

BLK

BLK

BLK

H2

RED

ORG

BLK/RED

X1

BLK

BLK

BLK

X2

WHT

WHT

WHT

X1

YEL

YEL

YEL

X2

BLU

BLU

BLU

Warning - First Stage Of
Thermostat Must Be
Connected To Terminals C1 &
C2 To Insure That Motor Will
Be Energized With First Stage
Heat Operation

Figure T

Contactors

AL3

AL2

AL1

BL1

BL2

BL3

Stage 2

Elements

C1

T3

T2

T1

Stage 1

Elements

C2

Stage 1

Stage 2

C1

C2

C3

Fan

2 Stage Thermostat
(By Others)

Cutouts

Optional Disconnect
Switch Built-in Or
Field Installed

Fuses

(When Req'd)

Fuses

KTK-3

L1 L2 L3

3 Phase,

60 HZ Power

Field Installed
Built-in Or Field Installed
Factory Wiring

31-00 33-00

T3

T2

T1

Warning - First Stage Of Thermostat
Must Be Connected To Terminals C1 & C2
To Insure That Motor Will Be Energized
With First Stage Heat Operation

Motor

Control Power

(By Others)

Note: For Single Stage
Thermostat, See Fig. M

Figure U

Field Installed
Built-in Or
Field Installed
Factory Wiring

Stage 2

Elements

Motor

Stage 1

Elements

C1

T1 T2

T3

C3

C2

C1

Contactor

(Typ.)

Stage 1

Fuses

(When Req'd)

BL1

BL2

BL3

3 Phase

60 HZ Power

AL1

AL2 AL3

Optional Disconnect
Switch Built-in Or
Field Installed

34-43 35-43

C4

C3

Heat

Fan

Stage 2

L1 L2 L3

Fuses KTK-3

2 PDT Switch

(By Others)

2 Stage Thermostat
(By Others)

Cutouts

C1
C4
C2
C3

4

2

1

3

Jumper

Fan

Heat

Thermostat

Jumpers

Thermostat

W/sub-base

(By Others)

Alternate Customer Hook Up (1 Stage)

Warning - First Stage Of Thermostat
Must Be Connected To Terminals C1 & C2
To Insure That Motor Will Be Energized
With First Stage Heat Operation

C2

T1T2

T3

Fan

Relay

Figure V

Field Installed
Built-in Or
Field Installed

Factory Wiring

Stage 2

Elements

Motor

Stage 1

Elements

C1

T1T2

T3

C3

C2

C1

Contactor

(Typ.)

Stage 1

Fuses

(When Req'd)

BL1

BL2

BL3

3 Phase

60 HZ Power

AL1

AL2 AL3

Optional Disconnect
Switch Built-in Or
Field Installed

31-45 33-45

C4

C3

Heat

Fan

Stage 2

L1 L2 L3

Fuses KTK-3

2 PDT Switch

(By Others)

2 Stage Thermostat
(By Others)

Cutouts

C1
C4
C2
C3

4

2

1

3

Jumper

Fan

Heat

Thermostat

Jumpers

Thermostat

W/sub-base

(By Others)

Alternate Customer Hook Up (1 Stage)

Warning - First Stage Of Thermostat
Must Be Connected To Terminals C1 & C2
To Insure That Motor Will Be Energized
With First Stage Heat Operation

C2

T1T2

T3

Fan
Relay

Control Power

(By Others)

Figure W

Field Installed

Built-in Or Field Installed
Factory Wiring

Transformer Color Code Index

Stage 2

Elements

Motor

Stage 1

Elements

C1

C2

T1T2T3

T1 T2T3

C3

C2

C1

X1

X2

H2

H1

Contactor

(Typ.)

XFMR

Stage 1

Fuses

(When Req'd)

BL1

BL2

BL3

3 Phase

60 HZ Power

AL1

AL2 AL3

Disconnect
Switch Built-in Or
Field Installed

30-45 32-45

C4

C3

Heat

Fan

Stage 2

L1 L2 L3

Fuses KTK-3

2 PDT Switch

(By Others)

2 Stage Thermostat
(By Others)

Cutouts

C1
C4
C2
C3

4

2

1

3

Jumper

Fan

Heat

Thermostat

Jumpers

Thermostat

W/sub-base

(By Others)

Alternate Customer Hook Up (1 Stage)

Warning - First Stage Of
Thermostat Must Be Connected
To Terminals C1 & C2
To Insure That Motor Will
Be Energized With First
Stage Heat Operation

PRI.
VOLT.

PRI. XFMR

LEAD CLRS.

120V SEC.

LEAD CLRS.

24V SEC.

LEAD CLRS.

208

240

480

H1

BLK

BLK

BLK

H2

RED

ORG

BLK/RED

X1

BLK

BLK

BLK

X2

WHT

WHT

WHT

X1

YEL

YEL

YEL

X2

BLU

BLU

BLU

Figure X