tekmar 132 Pump Sequencer User Manual
Data brochure, D 132, Pump sequencer 132
- Data Brochure
Pump Sequencer 132
D 132
04/10
1 of 12
© 2010 D 132 - 04/10
The Pump Sequencer 132 is designed to provide pump control for either stand-by or 2-stage operation. In stand-by mode, the 132
automatically switches over from the lead pump to the stand-by pump during a pump failure. In 2-stage mode, the 132 turns on the
second stage pump to meet additional flow requirements.
Additional functions include:
• Warm Weather Shut Down (WWSD)
• Exercising
• Equal Run Time Rotation
• Alert per Pump or Alert Levels
• Adjustable flow proof delay
• Test sequence to ensure proper component operation
• 120 V (ac) power supply
• CSA C US certified (approved to applicable UL standards)
Input
Outdoor
Sensor
Optional
Output
Pump
Pump
Input
120 V (ac) Power
Supply
Input
Pump
Demand
Signal
US
Made in Canada by
tekmar Control Systems Ltd.
Power:
Pump Relays:
Alert Relays:
Demands:
120 V ± 10% 60 Hz 6
VA
240 V (ac) 10 A 1/2 hp, pilot duty 720 VA
240 V (ac) 10 A 1/3 hp, pilot duty 240 VA
20 to 260 V (ac) 2 VA
Signal wiring
must be rate d
at least 300 V.
H1
197E
Test
1
2
Pump
Demand
3
4
2-Stage
Demand
5
6
Flow
Proof
8
9 10 11
12
1
1
2
7
17 18
Outdoor
Sensor
Pump
2
Clear Alert
Pump 1
Pump 2
Alert A
Alert B
Flow Proof
2-Stage Demand
Pump Demand
WWSD
Power
WWSD
35
Off
70°F
100
Frequency of Rotation
12
Off
96 hours
168
not testing
testing
testing paused
off
red
red
13 14
Alert
15 16
Alert
A
A
B
B
Input
2-Stage
Demand
Signal
Output
Do not apply power
Output
Alert
Output
Alert
2-Stage
Alert Levels
Pum p
1 2
Auto
30 second Delay
Exercising
Alert per Pump
Off
10 second Delay
Off
Stand-by
Pump Sequencer 132
Stand-by / 2-Stage
Input
Flow Proof
Signal
48
144
Use supply wires suitable for
120°F (50°C) above ambient
Pump
N
L
Power
Meets Class B
Canadian ICES
FCC Part 15
Note:
Pump demand must
be powered with 20 to
260 V (ac) before the
pump will turn on.